Home Categories Send inquiry

40 Amp Double Pole MCB






Responsive 3D Model





General

The YCB7-63N series miniature circuit breaker are suitable for overcurrent protection building line facilities and similar purposes in AC 50/60Hz, rated voltage 230V/400V, rated current up to 63A circuits. They have

isolation, overload, and short circuit protection functions, and can also be used for infrequent operation and switching of lines undernormal circumstances. Circuit breakers are suitable for various places such as

industry,commerce, high-rise buildings, and residential buildings.

Standard: IEC/EN 60898-1.

Applications

Manufacturing: Protect CNC machines, compressors, and conveyor systems.
Commercial Kitchens: Safeguard industrial ovens and refrigeration units.
HVAC Systems: Prevent overloads in high-capacity air handlers.

Selection

YCB7   63  N 1P   16 
Model   Shell grade
current
Breaking
capacity
Number
of poles
Tripping.
characteristics
Rated current
Miniature
circuit breaker
  63  N:6kA 1P
2P
3P
4P
B C D 1
2
4
6
10
16
20
25 
50
63

Note:This product can be assembled with accessories(YCB7-63N OF/SD/OF+SD/ MX/ MVMN/MX+OF, etc)

Technical data

Type Standard   IEC/EN 60898-1
Comprehensive
data
Function   Overload,Short circuit,Isolation
Number of poles   1P,2P,3P,4P
Rated current In A 1-63A
Rated frequency Hz 50/60Hz
Electrical
features
Rated voltage Ue V 230/400
Rated insulation voltage Ui V 500 
Rated breaking capacity Icn A 6000 
Rated impulse withstand voltage Uimp(1.2/50) kA
Pollution degree  
Use category   II、Ⅲ
Trip type   Thermal magnetic release
Thermal magnetic tripping characteristics   B,C,D
Electrical and mechanical accessories  
Mechanical
features
Mechanical life Times 20000 
Electrical life Times 10000 
Protection degree   IP20
Antihumidity and heat resistance   The relative humidity of the air is not more than 50%when
the ambient air temperature is +40℃,and it can have a
higher relative humidity at a lower temperature
Reference ambient temperature 30 
Ambient temperature -5°C-+40℃,the average value of 24h does not exceed+35℃
Height m Not exceeding 2000
Installation Terminal connection type   Cable/Pin-type busbar
Maximum
wire capacity
Terminal size
top/bottom for cable
 mm² 25 
 AWG 18-3
Terminal size
top/bottom for busbar
 mm² 25 
 AWG 18-3
Torque  N*m
In-Ibs 18 
Tool 18  Phillips screwdriver or flat-blade screwdriver
Installation   On DIN rail EN 60715(35mm)by means of fast clip device
Wiring method   From top or bottom

Overall and mounting dimensions(mm)

Selection

Type Test current Tripping time Expected result   Type Test current Tripping time Expected result
B,C,D 1.13In t≤1h(In≤63A) Not tripping   B 3In t≤0.1s Not tripping
1.13In t≤2h(In>63A)   C 5In t≤0.1s
B,C,D 1.45In t<1h(In≤63A) Tripping   D 10ln t≤0.1s
1.45In t<2h(In>63A)   B 5In t<0.1s Tripping
B,C,D 2.55In 1s Tripping   C 10ln t<0.1s
2.55In 1s32A)   D 20In t<0.1s

Curve

 

A Story of Reliability: How a Factory Saved Thousands with the Right MCB

1. Background

At a bustling small manufacturing plant in Chicago, managers prided themselves on meeting tight production deadlines. But behind the scenes, their aging electrical panels were a ticking time bomb.

2. The Challenge

The facility’s old circuit breakers frequently tripped during peak hours, halting assembly lines. Workers faced downtime, and repairs cost $5,000 monthly. Worse, a near-miss electrical fire revealed hidden risks.

3. The Conflict

“Every outage meant lost orders,” recalls the plant manager. “But upgrading the entire system was too expensive. We needed a fix that worked now.”

4. The Turning Point

An audit exposed the root cause: single-pole MCBs couldn’t handle fluctuating loads. The team realized they needed dual protection for both live and neutral lines.

5. The Solution

They installed the YCB7-63N 40A Double Pole MCB. With thermal-magnetic tripping and 20,000-cycle durability, it stopped overloads without nuisance trips.

6. The Results

Downtime reduced by 90% in 3 months.

$48,000 saved annually on repairs and lost productivity.

Zero safety incidents since installation.