The YBM22 series Box Type Transformer Substation is a fully integrated, compact power distribution solution that combines high-voltage and low-voltage equipment within a single, robust enclosure. Engineered for efficiency and reliability, it is designed to modernize electrical infrastructure across diverse settings.
Rated Voltage: High-Voltage side: 7.2KV / 12KV; Low-Voltage side: 0.4KV
Rated Current: High-Voltage side: 630A; Low-Voltage side: 100A to 2000A
Application: This prefabricated substation is ideally suited for power acceptance and distribution in 6-15KV, 50Hz/60Hz networks. It perfectly serves ring main, dual-power supply, and radial terminal distribution systems. Typical applications include high-rise buildings, urban and rural construction projects, residential complexes, tech parks, small-to-medium factories, mining areas, oil fields, and temporary construction sites.
Compliance Standard: IEC 1330
The standout feature of this Box Type Transformer Substation is its exceptional space-saving design. It offers a complete, safe, and reliable substation in a pre-assembled package, characterized by high structural integrity, a compact footprint, and easy maintenance. Compared to traditional civil-engineering substations of equivalent capacity, it reduces the required footprint by approximately 90-93% (using only 1/10 to 1/15 of the space), significantly lowering overall project costs and facilitating portable, flexible deployment.
1. Ambient air temperature: -10℃ ~+40℃
2. Altitude: ≤1000m
3. Solar radiation: ≤1000W/m²
4. Ice cover: ≤20mm
5. Wind speed: ≤35m/s
6. Relative humidity: Daily average relative humidity ≤95%.Monthly average relative humidity ≤90%
Daily average relative water vapour pressure ≤2.2kPa. Monthly average relative water vapour pressure ≤1.8kPa
7. Earthquake intensity: ≤magnitude 8
8. Applicable in the places without corrosive and flammable gas Note: Customized products are available
This Box Type Transformer Substation integrates high-voltage switchgear, a transformer, and low-voltage distribution equipment into three distinct, fully functional compartments: HV, Transformer, and LV.
The HV compartment supports various grid connections (ring-main, terminal, or dual-power supply) and can be fitted with metering devices. The transformer compartment accommodates low-loss options like S9 or SC series oil-immersed or dry-type transformers. The LV compartment can be configured with panel or cabinet structures to provide tailored solutions—including power distribution, lighting, power factor correction, and energy metering—enhancing management efficiency and power supply quality.
Designed with a compact and rational layout, the HV compartment features comprehensive interlocking for safety and can include rails for easy transformer maintenance. All compartments are equipped with automatic lighting. Components throughout the HV and LV cabinets are reliable and user-friendly.
Ventilation combines natural and forced methods, with dedicated channels in each compartment. Temperature-controlled exhaust fans in the transformer compartment auto-start based on set points, ensuring stable operation.
The enclosure is constructed from color steel plate, offering protection against rain, dust, and corrosion, with added insulation properties.
| Item | Unit | H.V electrical equipment | Transformer | L.V electrical equipment |
| Rated voltage | kV | 10 | 10/0.4 | 0.4 |
| Rated current | A | 630 | / | 100~2500 |
| Rated frequency | Hz | 50 | 50 | 50 |
| Rated capacity | kVA | 100~1250 | ||
| Rated thermal stability current | kA | 20/4S | / | 30/1S |
| Rated dynamic stability current (peak) | kA | 50 | / | 63 |
| Rated closing short-circuit current (peak) | kA | 50 | / | 15~30 |
| Rated breaking short circuit current | kA | 31.5 (Fuse) | / | / |
| Rated breaking load current | A | 630 | / | / |
| 1 min power frequency withstand voltage | kV | Between phases, to earth 42, to open contacts 48 |
35/28(5min) | 20/2.5 |
| Lightning impulse withstand voltage | kV | Between phases, to earth 75, to open contacts 85 |
75 | / |
| Shell protection class | IP23 | IP23 | IP23 | |
| Noise level | dB | 630 | Oil transformer ≤55 Dry transformer ≤65 | / |
| Loops No. | / | 2 | 4~30 | |
| Low voltage side max static var compensator | kvar | / | / | 300 |
YBM series of prefabricated substation have type 1 (refer pic1-1, 1-2) and type 2 (refer to 1-3, 1-4), the Overall and mounting dimensions(mm) s refer to pic 2, pic 3.
YBM series of prefabricated substation plane layout
High voltage loop scheme
Low voltage loop scheme
Terminal low measurement
Terminal high measurement
Looped network Low measurement
Looped network high measurement
1. The type of prefabricated substation
2. The type and capacity of power transformer
3. High voltage and low voltage single line scheme
4. Electrical component models and parameters if have special requirement
5. Shell color
6. The spare parts, name, quantity and other requirements