YCB7-125N MCB Miniature circuit breaker



General

YCB7-125N miniature circuit breaker(circuit breaker)is applicable to the circuit with AC50 Hz/60Hz, rated voltage of no more than400 V,and rated current from 10A to 125A for overload protection and short circuit protection. This product can be applied to various places such as industrial, commercial, tall buildings, and residential houses.

Standard: IEC 60947-2、IEC 60947-2 IEC 60898-1

Operating conditions

1. Ambient air temperature -5°C ~+40°C (with daily average≤35°C)

2. Altitude:≤2000m.

3. Air conditions: At mounting site, relative humidity not exceed 50% at the maximum temperature of +40°C. For the wettest month, the maxi

mum relative humidity averaged shall be 90% while the lowest temperature averaged in that month is +20°C , special measures should be

taken to occurrence of condensation.

4. The installation category is Ⅲ .

5. The circuit breaker shall be installed on DIN rail EN 60715(35mm), which shall meet theA1.1 TH 35-7.5 steel mounting rail requirements.

6. Pollution grade: 3

7. Mounting conditions: inclination between mounting plane and vertical plane not exceed±5°.

8. The product should locate in the places where there are no obvious impact and shake.

Table 1
Ui Uimp Number of
poles
Rated
frequency HZ
Rated voltage Ue Rated Current
In
Thermomagnetic
release characteristic
Rated circuit
breaking capacity Icn
500V 6kV 1P/2P 50/60 AC230V/400V 10-125A (C)li=8In, 6kAli=12In
3P/4P AC400V

Release

Type Test current Tripping time Expected result
C,D 1.05In t≤1h(In≤63A),t≤2h(In≤63A) Not tripping
C,D 1.3In t≤1h(In≤63A),t≤2h(In≤63A) Tripping
C,D 2.55In 1s<t<60s Tripping
C 8ln×80% t≤0.2s Not tripping
D 12In×80% t≤0.2s Not tripping
C 8ln×120% t<0.2s Tripping
D 12In×120% t<0.2s Tripping

Specifications

Type Standard   IEC/EN 60947-2 IEC/EN 60898-1
Electrical
features
Rated current In A 10,16,20,25,40,50,63,80,100,125
Poles P 1,2,3,4
Rated voltage Ue V 230/400
Insulation voltage Ui V 500 
Rated frequency Hz 50/60
Rated breaking capacity A 6000 
Rated impulse withstand voltage(1.2/50)Uimp V 6000 
Dielectric test voltage at ind.Freq.for 1min kV 2.5 
Pollution degree  
Thermo-magnetic release characteristic   (C)li=8In,(D)li=12In
Mechanical
features
Electrical life t 1500 
Mechanical life t 8500 
Contact position indicator   Yes
Protection degree   IP20
Reference temperature for setting
of thermal element
  30 
Ambient temperature
(with daily average ≤35℃)
-5~+40(Special application please refer to
temperature compensation correction)
Storage temperature -25~+70
Installation Terminal connection type Cable/Pin-type busbar
Terminal size top/bottom for cable  mm² 50 
 AWG 18-1/0
Terminal size top/bottom for busbar  mm² 50 
 AWG 18-1/0
Tightening torque  N*m 3.5 
In-lbs 31 
Mounting   On DIN rail EN60715(35mm)by means of fast clip device
Connection   From top and bottom

Overall and mounting dimensions(mm)

Ordering instructions

1. When ordering, the customer shall indicate the product type, tripping curve, rated current, number of poles, accessories and quantity of the circuit breaker. For example: YCB7- 125N 3P C100 1000pcs.

2. Customers can negotiate separately if you have special requirements.