YCB7-125N miniature circuit breaker(circuit breaker)is applicable to the circuit with AC50 Hz/60Hz, rated voltage of no more than400 V,and rated current from 10A to 125A for overload protection and short circuit protection. This product can be applied to various places such as industrial, commercial, tall buildings, and residential houses.
Standard: IEC 60947-2、IEC 60947-2 IEC 60898-1
1. Ambient air temperature -5°C ~+40°C (with daily average≤35°C)
2. Altitude:≤2000m.
3. Air conditions: At mounting site, relative humidity not exceed 50% at the maximum temperature of +40°C. For the wettest month, the maxi
mum relative humidity averaged shall be 90% while the lowest temperature averaged in that month is +20°C , special measures should be
taken to occurrence of condensation.
4. The installation category is Ⅲ .
5. The circuit breaker shall be installed on DIN rail EN 60715(35mm), which shall meet theA1.1 TH 35-7.5 steel mounting rail requirements.
6. Pollution grade: 3
7. Mounting conditions: inclination between mounting plane and vertical plane not exceed±5°.
8. The product should locate in the places where there are no obvious impact and shake.
Table 1 | |||||||
Ui | Uimp | Number of poles |
Rated frequency HZ |
Rated voltage Ue | Rated Current In |
Thermomagnetic release characteristic |
Rated circuit breaking capacity Icn |
500V | 6kV | 1P/2P | 50/60 | AC230V/400V | 10-125A | (C)li=8In, | 6kAli=12In |
3P/4P | AC400V |
Type | Test current | Tripping time | Expected result |
C,D | 1.05In | t≤1h(In≤63A),t≤2h(In≤63A) | Not tripping |
C,D | 1.3In | t≤1h(In≤63A),t≤2h(In≤63A) | Tripping |
C,D | 2.55In | 1s<t<60s | Tripping |
C | 8ln×80% | t≤0.2s | Not tripping |
D | 12In×80% | t≤0.2s | Not tripping |
C | 8ln×120% | t<0.2s | Tripping |
D | 12In×120% | t<0.2s | Tripping |
Type | Standard | IEC/EN 60947-2 | IEC/EN 60898-1 | |
Electrical features |
Rated current In | A | 10,16,20,25,40,50,63,80,100,125 | |
Poles | P | 1,2,3,4 | ||
Rated voltage Ue | V | 230/400 | ||
Insulation voltage Ui | V | 500 | ||
Rated frequency | Hz | 50/60 | ||
Rated breaking capacity | A | 6000 | ||
Rated impulse withstand voltage(1.2/50)Uimp | V | 6000 | ||
Dielectric test voltage at ind.Freq.for 1min | kV | 2.5 | ||
Pollution degree | 3 | |||
Thermo-magnetic release characteristic | (C)li=8In,(D)li=12In | |||
Mechanical features |
Electrical life | t | 1500 | |
Mechanical life | t | 8500 | ||
Contact position indicator | Yes | |||
Protection degree | IP20 | |||
Reference temperature for setting of thermal element |
30 | |||
Ambient temperature (with daily average ≤35℃) |
℃ | -5~+40(Special application please refer to temperature compensation correction) |
||
Storage temperature | ℃ | -25~+70 | ||
Installation | Terminal connection type | ℃ | Cable/Pin-type busbar | |
Terminal size top/bottom for cable | mm² | 50 | ||
AWG | 18-1/0 | |||
Terminal size top/bottom for busbar | mm² | 50 | ||
AWG | 18-1/0 | |||
Tightening torque | N*m | 3.5 | ||
In-lbs | 31 | |||
Mounting | On DIN rail EN60715(35mm)by means of fast clip device | |||
Connection | From top and bottom |
1. When ordering, the customer shall indicate the product type, tripping curve, rated current, number of poles, accessories and quantity of the circuit breaker. For example: YCB7- 125N 3P C100 1000pcs.
2. Customers can negotiate separately if you have special requirements.