High breaking capacity
Strong applicability of attachments
Small volume
Anti slip design
Stable and reliable
YCB7LE | 一 | 63 | Y | 1P+N | C | 63 | 100mA | AType |
Model | Shell grade current |
Category | Pole | Tripping characteristics |
Rated current |
Rated residua operating |
Type | |
Residual Current Operated Circuit Breaker |
一 | 63 | Integrated | 1P+N | B C D |
6 10 16 20 25 32 40 50 63 |
Default:30mA 100mA 300mA |
Default:AC Type A Type |
There are six different accessories in the circuit breaker,including OF auxiliary contact,MX+OF shunt release,SD alarm contact,MV overvoltage release,MN undervoltage release,and MVMN overvoltage and undervoltage release.All accessories are installed on the leftside of the product.
Model | YCB7LE-63Y | ||
Electrical features |
Poles | P | 1P+N |
Type(wave form of the earth leakage sensed) | AC、A | ||
Thermomagnetic release characteristic | B,C,D | ||
Rated current In | A | 6,10,16,20,25,32,40,50,63 | |
Rated voltage Ue | V | 230 | |
Rated sensitivity I△n | A | 0.03,0.1,0.3 | |
Rated residual making and breaking capacity I△m | A | 630 | |
Rated short-circuit capacity Icn | A | 6000 | |
Break time under I△n | S | ≤0.1 | |
Rated frequency | Hz | 50/60 | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |
Dielectric test voltage at ind.Freq.for1min | Kv | 2 | |
Insulation voltage Ui | V | 500 | |
Pollution degree | 2 | ||
Mechanical features |
Electrical life | t | 10000 |
Mechanical life | t | 20000 | |
Contact position indicator | Yes | ||
Protection degree | t | IP20 | |
Ambient temperature(with daily average≤35℃) | ℃ | -5~+40 | |
Storage temperature | ℃ | -25~+70 | |
Installation | Terminal connection type | Cable/Pin-type busbar | |
Terminal size top/bottom for cable | mm² | 25 | |
AWG | 18-3 | ||
Terminal size top/bottom for busbar | mm² | 25 | |
AWG | 18-3 | ||
Tightening torque | N*m | 2 | |
In-Ibs | 18 | ||
Mounting | On DIN rail EN60715(35mm)by means of fast clip device | ||
Connection | From top |