YCB9-63R Series Miniature Circuit Breaker

General

YCB9-63R Series Miniature circuit breaker is applicable to protecting from overload and short circuit in the circuit ofAC50/60Hz,Rated volt-age 230/400V rated curent 63A,t also can be used in switch the infequent operation of the circuit under normal conditions.It's mainly used inindustry,commerce,high-rise buildings and residential houses and so on.

Standard:IEC 60898-1

Feature

1.Overload protection

2.Short circuit protection

3.Controlling

4.Used in residential building,non-residential building,energy source industry and infrastructure

5.According to the type of instantaneous release classified as follows:type B(3-5)In,type C(5-10)In,type D(10-20)In

Type designation

 

Operating conditions

1.Circumstance temperature-5℃~+40℃,average temperature within 24h not exceeding+35℃.

2.Altitude above sea level less than 2000m.

3.Humidity not exceeding 50%at 40℃ and not exceeding 90%at 25℃.

4.Pollution class 2.

5.Installation class Il orⅢ.

6.Installation method DIN Railmounting type.

7.Product shall be installed at the place where there shall be no severe impact and vibration.

8.The product should locate in the places where there are no obvious impact and shake.

Selection

Type Test current Tripping time Expected result   Type Test current Tripping time Expected result
B,C,D 1.13In t≤1h(In≤63A) Not tripping B 3In t≤0.1 Not tripping
1.13In t≤2h(In>63A) C 5In t≤0.1s
B,C,D 1.45In t≤1h(In≤63A) Tripping D 10ln t≤0.1s
1.45In t<2h(In>63A) B 5In t<0.1s Tripping
B,C,D 2.25In 1s<t<60s(In≤32A) Tripping         C 10ln t<0.1s
2.25In 1s<t<120s(In>32A) D 20ln t<0.1s

Curve

 

Technical data

Type Standard   IEC/EN 60898-1
Electrical
features
Rated current In A 1.2,4,6,10,16,20,25,32.40,50,63 1,2,4,6,10,16,20,25,32,40
Poles P 1,2,3,4
Rated voltage Ue V 230/400
Insulation voltage Ui V 500 
Rated frequency Hz 50/60
Rated breaking capacity A 15000A 25000A
Rated impulse withstand voltage(1.2/50)Uimp V 4000 
Dielectric test voltage at ind.Freg.for 1min kV
Pollution degree  
Thermo-magnetic release characteristic   B,C,D
Mechanical
features
Electrical life t 8000 
Mechanical life t 20000 
Protection degree   IP40
Reference temperature for setting of thermal element 30 
Ambient temperature (with daily average≤35℃) -5~+40
Storage temperature -25~+70
Installation Terminal connection type   Cable/Pin-type busbar
Terminal size top/bottom for cable   mm² 25 
  AWG 18-3
Terminal size top/bottom for busbar   mm² 25 
  AWG 18-3
Tightening torque   N*m
In-lbs 18 
Mounting   On DIN rail EN 60715(35mm)by means of fast clip
Connection   From top or bottom
Before  installation,check  whether  technical  parameter  of the  circuit  breaker  is  in  conformity  with  user's  requirement.The  conductor  of  power
supply shall  be  connected to the  up terminal  of circuit  breaker.During  installation,the tightening torque  is  max 2.5N·m.The sectional  area  of
connecting wire can refer to Table 1.
   Table  1
Rated current InA Conductor cross section S mm²
10  1.5 
1,620 2.5 
25 
32 
4,050 10 
63  16 

Temperature drop correction table

The maximum allowable curent of the circuit breaker is related to the ambient temperature of the circuit breaker.The ambient temperature re-fers to the temperature in the distribution box or switch cabinet where the circuit breaker i installed.The reference temperature of various circuitbreakers can be found in the values of the colored rows in the table.

Product standard:GB/T10963.1 IEC60898-1 (household standard)

temperature(℃) -5  10  15  20  25  30  35  40  45 
Rated current                      
1A 1.16  1.14  1.11  1.09  1.07  1.05  1.02  1.00  0.98  0.95  0.92 
2A 2.30  2.26  2.22  2.18  2.13  2.08  2.04  2.00  1.96  1.92  1.88 
4A 4.72  4.63  4.53  4.43  4.32  4.22  4.11  4.00  3.89  3.77  3.65 
6A 6.97  6.84  6.71  6.57  6.43  6.29  6.15  6.00  5.85  5.69  5.53 
10A 12.25  11.95  11.65  11.34  11.02  10.69  10.35  10.00  9.64  9.26  8.86 
16A 18.72  18.35  17.98  17.60  17.22  16.82  16.42  16.00  15.57  15.13  14.68 
20A 23.24  22.80  22.36  21.91  21.45  20.98  20.49  20.00  19.49  18.97  18.44 
25A 29.12  28.57  28.01  27.43  26.85  26.24  25.63  25.00  24.35  23.69  23.01 
32A 37.18  36.49  35.78  35.05  34.32  33.56  32.79  32.00  31.19  30.36  29.50 
40A 46.66  45.77  44.86  43.93  42.98  42.01  41.02  40.00  38.96  37.88  36.78 
50A 58.57  57.43  56.26  55.06  53.84  52.59  51.31  50.00  48.65  47.27  45.84 
63A 74.73  73.17  71.57  69.94  68.27  66.56  64.81  63.00  61.14  59.22  57.24 

Overall and mounting dimensions (mm)

 

Operating conditions

1. When ordering, the customer shall indicate the product type, tripping curve, rated current, number of poles, accessories and quantity of the circuit breaker. For example: YCB9-63R C25 3P 880pcs.

2. Customers can negotiate separately if you have special requirements.