YCB9-63R Series Miniature circuit breaker is applicable to protecting from overload and short circuit in the circuit ofAC50/60Hz,Rated volt-age 230/400V rated curent 63A,t also can be used in switch the infequent operation of the circuit under normal conditions.It's mainly used inindustry,commerce,high-rise buildings and residential houses and so on.
Standard:IEC 60898-1
1.Overload protection
2.Short circuit protection
3.Controlling
4.Used in residential building,non-residential building,energy source industry and infrastructure
5.According to the type of instantaneous release classified as follows:type B(3-5)In,type C(5-10)In,type D(10-20)In
1.Circumstance temperature-5℃~+40℃,average temperature within 24h not exceeding+35℃.
2.Altitude above sea level less than 2000m.
3.Humidity not exceeding 50%at 40℃ and not exceeding 90%at 25℃.
4.Pollution class 2.
5.Installation class Il orⅢ.
6.Installation method DIN Railmounting type.
7.Product shall be installed at the place where there shall be no severe impact and vibration.
8.The product should locate in the places where there are no obvious impact and shake.
Type | Test current | Tripping time | Expected result | Type | Test current | Tripping time | Expected result | |
B,C,D | 1.13In | t≤1h(In≤63A) | Not tripping | B | 3In | t≤0.1 | Not tripping | |
1.13In | t≤2h(In>63A) | C | 5In | t≤0.1s | ||||
B,C,D | 1.45In | t≤1h(In≤63A) | Tripping | D | 10ln | t≤0.1s | ||
1.45In | t<2h(In>63A) | B | 5In | t<0.1s | Tripping | |||
B,C,D | 2.25In | 1s<t<60s(In≤32A) | Tripping | C | 10ln | t<0.1s | ||
2.25In | 1s<t<120s(In>32A) | D | 20ln | t<0.1s |
Type | Standard | IEC/EN 60898-1 | ||
Electrical features |
Rated current In | A | 1.2,4,6,10,16,20,25,32.40,50,63 | 1,2,4,6,10,16,20,25,32,40 |
Poles | P | 1,2,3,4 | ||
Rated voltage Ue | V | 230/400 | ||
Insulation voltage Ui | V | 500 | ||
Rated frequency | Hz | 50/60 | ||
Rated breaking capacity | A | 15000A | 25000A | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | ||
Dielectric test voltage at ind.Freg.for 1min | kV | 2 | ||
Pollution degree | 2 | |||
Thermo-magnetic release characteristic | B,C,D | |||
Mechanical features |
Electrical life | t | 8000 | |
Mechanical life | t | 20000 | ||
Protection degree | IP40 | |||
Reference temperature for setting of thermal element | ℃ | 30 | ||
Ambient temperature (with daily average≤35℃) | ℃ | -5~+40 | ||
Storage temperature | ℃ | -25~+70 | ||
Installation | Terminal connection type | Cable/Pin-type busbar | ||
Terminal size top/bottom for cable | mm² | 25 | ||
AWG | 18-3 | |||
Terminal size top/bottom for busbar | mm² | 25 | ||
AWG | 18-3 | |||
Tightening torque | N*m | 2 | ||
In-lbs | 18 | |||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip | |||
Connection | From top or bottom | |||
Before installation,check whether technical parameter of the circuit breaker is in conformity with user's requirement.The conductor of power supply shall be connected to the up terminal of circuit breaker.During installation,the tightening torque is max 2.5N·m.The sectional area of connecting wire can refer to Table 1. |
||||
Table 1 |
Rated current InA | Conductor cross section S mm² |
6 | 1 |
10 | 1.5 |
1,620 | 2.5 |
25 | 4 |
32 | 6 |
4,050 | 10 |
63 | 16 |
The maximum allowable curent of the circuit breaker is related to the ambient temperature of the circuit breaker.The ambient temperature re-fers to the temperature in the distribution box or switch cabinet where the circuit breaker i installed.The reference temperature of various circuitbreakers can be found in the values of the colored rows in the table.
Product standard:GB/T10963.1 IEC60898-1 (household standard)
temperature(℃) | -5 | 0 | 5 | 10 | 15 | 20 | 25 | 30 | 35 | 40 | 45 |
Rated current | |||||||||||
1A | 1.16 | 1.14 | 1.11 | 1.09 | 1.07 | 1.05 | 1.02 | 1.00 | 0.98 | 0.95 | 0.92 |
2A | 2.30 | 2.26 | 2.22 | 2.18 | 2.13 | 2.08 | 2.04 | 2.00 | 1.96 | 1.92 | 1.88 |
4A | 4.72 | 4.63 | 4.53 | 4.43 | 4.32 | 4.22 | 4.11 | 4.00 | 3.89 | 3.77 | 3.65 |
6A | 6.97 | 6.84 | 6.71 | 6.57 | 6.43 | 6.29 | 6.15 | 6.00 | 5.85 | 5.69 | 5.53 |
10A | 12.25 | 11.95 | 11.65 | 11.34 | 11.02 | 10.69 | 10.35 | 10.00 | 9.64 | 9.26 | 8.86 |
16A | 18.72 | 18.35 | 17.98 | 17.60 | 17.22 | 16.82 | 16.42 | 16.00 | 15.57 | 15.13 | 14.68 |
20A | 23.24 | 22.80 | 22.36 | 21.91 | 21.45 | 20.98 | 20.49 | 20.00 | 19.49 | 18.97 | 18.44 |
25A | 29.12 | 28.57 | 28.01 | 27.43 | 26.85 | 26.24 | 25.63 | 25.00 | 24.35 | 23.69 | 23.01 |
32A | 37.18 | 36.49 | 35.78 | 35.05 | 34.32 | 33.56 | 32.79 | 32.00 | 31.19 | 30.36 | 29.50 |
40A | 46.66 | 45.77 | 44.86 | 43.93 | 42.98 | 42.01 | 41.02 | 40.00 | 38.96 | 37.88 | 36.78 |
50A | 58.57 | 57.43 | 56.26 | 55.06 | 53.84 | 52.59 | 51.31 | 50.00 | 48.65 | 47.27 | 45.84 |
63A | 74.73 | 73.17 | 71.57 | 69.94 | 68.27 | 66.56 | 64.81 | 63.00 | 61.14 | 59.22 | 57.24 |
1. When ordering, the customer shall indicate the product type, tripping curve, rated current, number of poles, accessories and quantity of the circuit breaker. For example: YCB9-63R C25 3P 880pcs.
2. Customers can negotiate separately if you have special requirements.