YCB9-80M/H Miniature Circuit Breaker MCB

General

The YCB9-80 series miniature circuit breaker are suitable for overcurrent protection of building line facilities and similar purposes in AC 50/60Hz, rated voltage 230V/400V, rated current up to 80A circuits. They have isolation, overload, and short circuit protection functions, and can also be used for infrequent operation and switching of lines under normal circumstances.Circuit breakers are suitable for various places such as industry, commerce, high-rise buildings, and residential buildings.

Standard:IEC/EN 60898-1,IEC/EN 60947-2

 

YCB9 80  M 1P C 16  Double busbar
Model Frame size rated current Breaking
capacity
Number
of poles
Tripping
characteristics
Rated
current
Others
Miniature
circuit breaker
80  M:6kA
H:10kA
1P
2P

3P
4P

B
C

D

1
2
4
6
10
16
20
25
32
40
50
63
80

/:Single busbar
DB:Double
busbar

Note: This product c)an be assembled with accessories(YCB9-80 OF/SD/OF+SD/ MX/ MVMN/MX+OF, etc

Technical data

Type Standard   IEC/EN 60947-2 IEC/EN 60898-1
Comprehensive
data
Function   Overload,Short circuit,Isolation
Number of poles   1P,2P,3P,4P
Rated current In A 1-63A 1-80A
Rated frequency Hz 50/60Hz
Electrical
features
Rated voltage Ue V 230/400
Rated insulation voltage Ui V 500 
Rated breaking capacity Icn A M:6000 H:10000
Rated impulse withstand voltage Uimp(1.2/50) kA
Pollution degree  
Use category   II,IⅢ
Trip type   Thermal magnetic release
Thermal magnetic tripping characteristics   8.5-12In B,C,D
Electrical and mechanical accessories  
Mechanical
features
Mechanical life times 20000 
Electrical life times 10000 
Protection degree   IP20
Antihumidity and heat resistance   The relative humidity of the air is not more than 50%when
the ambient air temperature is +40℃,and it can have a
higher relative humidity at a lower temperature
Reference ambient temperature 30 
Ambient temperature -5℃-+40℃,the average value of 24h does not exceed
+35℃
Height m Not exceeding 2000
Installation Busbar connection type   Single or Double bus bar Anti-mistake contact terminal block
Terminal connection type   Cable/U-type busbar/Pin-type busbar
Maximum wire
capacity
Terminal size top/bottom for cable   mm² 25 
  AWG 18-3
Terminal size top/bottom for busbar   mm² 25 
  AWG 18-3
Torque   N*m
In-lbs 18 
Tool 18  Phillips screwdriver or flat-blade screwdriver
Installation   On DIN rail EN 60715(35mm)by means of fast clip device
Wiring method   From top or bottom

Overall and mounting dimensions(mm)

 

Tripping characteristic(IEC/EN 60898-1)

Type Test current Tripping time Expected result Type Test current Tripping time Expected result
B,C,D 1.13In t≤1h(In≤63A) Not tripping B 3In t≤0.1s Not tripping
1.13In t≤2h(In>63A) C 5In t≤0.1s
B,C,D 1.45In t≤1h(In≤63A) Tripping D 10ln t≤0.1s
1.45In t<2h(In>63A) B 5In t<0.1s Tripping
B,C,D 2.25In 1s<t <60s(In≤32A)  Tripping C 10ln t<0.1s
2.25In 1s<t<120s(In>32A) D 20ln t<0.1s

Tripping characteristic(IEC/EN 60947-2)

Test Rated
curent
Test
current
Initial status Time limit for tripping
or not tripping
Time limit for tripping
or not tripping
Remarks
a 1-63A 1.05In Cold state t≥1h(In≤63A)
t≥2h(In>63A)
Not tripping Current increase steadily within 5s
b 1.3In Right after
test number a
t<1h(In≤63A)
t<2h(In>63A)
Tripping
C 8ln Cold state t≥0.2s Not tripping Turn on the power supply byclosing the auxiliary switch
d 12In Cold state t<0.2s Not tripping Turn on the power supply byclosing the auxiliary switch

Curve