Technical data
Conventional thermal current(A) |
|
160 |
250 |
400 |
630 |
Rated insulation voltage(V) |
|
800 |
|||
Rated current(A) |
400V |
160 |
250 |
400 |
630 |
AC20 |
|||||
400V |
160 |
250 |
400 |
630 |
|
AC21 |
|||||
400V |
160 |
250 |
400 |
630 |
|
Ac22 |
|||||
690V |
160 |
250 |
400 |
630 |
|
Ac20 |
|||||
690V |
100 |
200 |
315 |
425 |
|
Ac21 |
|||||
690V |
100 |
160 |
315 |
315 |
|
Ac22 |
|||||
Specification of a ssociatedfuse |
Model |
00 |
1 |
2 |
3 |
400V Rated current of fuse (Breaking capactiy) A |
20,25,32,35, 40,50,63,80, 100,125, 160(≥100kA) |
80,100,125, 160,200,224, 250(≥100kA) |
125,160,200, 224,250,315, 355,400(≥100kA) |
315,355,400, 425,500,630 ( ≥100kA) |
|
690V Rated current of fuse (Breaking capactiy) A |
20,25,32,35, 40,50,63,80, 100(≥50kA) |
80,100,125, 160,200(≥50kA) |
125,160,200, 224,250,300, 315(≥50kA) |
315,355, 400,425 ( ≥50kA) |
Overall and mounting dimensions(mm)
Model |
Bus bar(mm) |
Fuse link |
Note |
YCH5-160 |
185 |
NT00 |
Independent operation phase to phase |
YCH5-160L |
185 |
NT00 |
Three phases breaking and making simultaneously |
Model |
Bus bar(mm) |
Fuse link |
Note |
YCH5-250L |
185 |
NH1 |
Three phases breaking and making simultaneously |
YCH5-400L |
185 |
NH2 |
|
YCH5-630L |
185 |
NH3 |
|
YCH5-250 |
185 |
NH1 |
Independent operation phase to phase |
YCH5-400 |
185 |
NH2 |
|
YCH5-630 |
185 |
NH3 |