Technical data
| Rated Operating Voltage Uc(V~) | 220V | 380V | 220V | 380V | |
| Maximum Continuous Operating Voltage Uc(V~) | 275V | 385V | 275V | 385V | |
| Voltage Protection Level Up(V~)kV | ≤0.7 | ≤1.0 | ≤1.2 | ≤1.5 | |
| Nominal Discharge Current In(8/20μs)kA | 10 | ||||
| Maximum Discharge Current Imax(8/20μs)kA | 10 | 20 | |||
| Response Time ns | <25 | ||||
| Test Standard | IEC61643-1 | ||||
| L/N(mm2)The Cross Section of L/N Line | 2.5 | ||||
| PE(mm2)The Cross Section of PE Line | 6 | ||||
| Fuse or Switch(A | 10A,16A | 16A,25A | |||
| Operating EnvironmentC | -40℃~+85℃ | ||||
| Relative Humidity(25℃) | ≤95% | ||||
| Installation | d 35 | ||||