Type designation
1. Rated current in scope of frame current
2000 Type-in: 630A, 800A, 1000A, 1250A, 1600A, 2000A;
3200 Type-in: 2000A, 2500A, 3200A;
6300 Type-in: 4000A, 5000A, 6300A;
2. Pole number
3-default, 4-4 pole
3. Installation
Fixed type-horizontal, vertical
Draw out type-horizonal, vertical
Note: 2000 type have vertical wiring, others are horizontal wiring
4. Control unit
L type-dial switch mode, over-current protection (overload, short delay,
instantaneous).
2M type-digitaldisplay,over-current protection (overload, shortdelay,
instantaneous), 4P or 3P+N have earthing protection (3M type is LCD display).
2H type-communication function, digital display, over-current protection
(overload, short delay, instantaneous), 4P or 3P+N have earthing protection (3H
type is LCD display).
5. Common use accessory
Closing electromagnet-AC230V, AC400V, DC220V
Undervoltage release-AC230V, AC400V, undervoltage instantaneous,
undervoltage time-delay
Release (close) magnetic iron-AC230V, AC400V, DC220V
Electric operation mechanism-AC230V, AC400V, DC110V, DC220V
Auxiliary contact-standard type (4a4b), special type (5a5b, 6a6b)
Note: a-normal open, b-normal close
6. Optional accessory
Mechanical inter-lock:
one circuit breaker (1lock+1key)
two circuit breaker (steel cable inter-lock, connecting rod inter-lock, 2lock+1key)
three circuit breakers (3locks+2keys, connecting rod inter lock)
Automatic power transfer system
Current transformer connected with neutral lead
Operation Conditions
| Operating conditions |
| Item |
Description |
| Ambient temperature |
-5℃~+40℃ (except special order products) |
| Altitude |
≤2000m |
| Pollution grade |
3 |
| Safety category |
Main circuit and undervoltage tripping coil is IV, other auxiliary and control circuit is III |
| Installation position |
Vertical installed, tilt not exceed 5 degree |
| Environmental protection |
Most of parts use recyclable and degradable materials |
| Isolating function |
With isolating function |
Specifications
Curves
Data
| Type |
|
YCW1-2000 |
YCW1-3200 |
YCW1-6300 |
| Pole |
|
3P, 4P |
3P, 4P |
3P, 4P |
| Using category |
|
B |
B |
B |
| Rated current In |
A |
630, 800, 1000,1250, 1600, 2000 |
2000, 2500, 3200 |
4000, 5000, 6300 |
| Rated frequency |
Hz |
50 |
50 |
50 |
| Rated operation voltage Ue |
V |
400, 690 |
400, 690 |
400, 690 |
| Rated insulation voltage Ui |
V |
800 |
800 |
800 |
| Arcing distance |
mm |
0 |
0 |
0 |
| Rated impulse withstanding voltage Uimp |
V |
8000 |
8000 |
8000 |
| Rated operation short circuit breaking capacity Ics (O-t-CO) |
400V |
kA |
50 |
80 |
100 |
| 660V |
kA |
40 |
50 |
75 |
| Rated limiting short circuit |
400V |
kA |
80 |
80 |
120 |
| breaking capacity Icu (O-t-CO) |
660V |
kA |
50 |
65 |
85 |
| Rated short time withstanding current Icw (O-t-CO, AC400V 0.4S) |
400V |
kA |
50 |
65 |
85 |
| Operation life |
Per hour |
times |
20 |
20 |
10 |
| Electrical |
times |
1000 |
500 |
500 |
| Mechanical |
times |
10000 |
5000 |
5000 |
| Full breaking time |
|
ms |
20~30 |
20~30 |
20~30 |
| Full closing time |
|
ms |
55~70 |
55~70 |
55~70 |
| Power consumption |
3P |
W |
360 |
1200 |
2000 |
| 4P |
W |
450 |
1750 |
2300 |
| Resistance of each pole |
Fixed type |
μΩ |
11 |
9 |
- |
| Draw out type |
μΩ |
20 |
14 |
10 |
| Dimensions (L ×W × H) |
3P fixed type |
mm |
362 ×323 ×402 |
422 ×323 ×402 |
|
| 3P draw out type |
mm |
375 ×461 ×452 |
435 ×471 ×452 |
|
| 4P fixed type |
mm |
457 ×323 ×402 |
537 ×323 ×402 |
|
| 4P draw out type |
mm |
470 ×461 ×452 |
550 ×471 ×452 |
|
| Approximate weight |
3P fixed type |
kg |
41 |
55 |
|
| 3P draw out type |
kg |
71 |
95 |
245 |
| 4P fixed type |
kg |
51.5 |
65 |
- |
| 4P draw out type |
kg |
86 |
115 |
260 |
Overload protection data
| Overload protection |
YCW1-2000~6300 |
| Adjust scope Ir1 |
|
(0.4-1)In (pole difference 2%) |
| 1.05 Ir1 |
h |
2h non-tripping |
| 1.3 Ir1 |
h |
≤1h tripping |
| 1.5 Ir1 |
s |
15 |
30 |
60 |
120 |
240 |
480 |
| 2.0 Ir1 |
s |
8.4 |
16.9 |
33.7 |
67.5 |
135 |
270 |
| Accuracy |
% |
±15 |
| Short circuit, short time delay |
|
| Adjust scope Ir1 Ir2 |
|
(0.4-15)In (pole difference 2%) |
| Delay time tr2 |
ms |
100, 200, 300, 400 |
| Accuracy |
% |
±15 |
| Short circuit, instantaneous |
|
|
YCW1-2000 |
YCW1-3200 |
YCW1-6300 |
| Adjust scope Ir1 Ir3 |
|
1In-50kA |
1In-75kA |
1In-100kA |
| Accuracy |
% |
±15 |
±15 |
±15 |
| Load monitoring output |
YCW1-2000~6300 |
| Load adjust scope Ic1 |
|
(0.2-1)In (pole difference 2%) |
| Delay time tc1 |
|
tr1 ×0.5 |
| Load adjust scope Ic2 |
|
(0.2-1)In (pole difference 2%) |
| Delay time tc2 |
|
tr1 ×0.25 (anti-time limit) |
| Accuracy |
s |
60 (set time limit) |
| % |
±10 |
Overall and mounting dimensions
Installation and figure dimension of YCW1-2000A fixed type circuit breaker
Installation and figure dimension of YCW1-3200A fixed type circuit breaker
Installation and figure dimension of YCW1-4000A fixed type circuit breaker
Installation and figure dimension of YCW1-6300A fixed type circuit breaker
Installation and figure dimension of YCW1-2000A draw-out type circuit breaker
Installation and figure dimension of YCW1-3200A draw-out type circuit breaker
Installation and figure dimension of YCW1-4000A draw-out type circuit breaker
Installation and figure dimension of YCW1-4000A(4P) draw-out type circuit breaker
Installation and figure dimension of YCW1-6300A draw-out type circuit breaker
Installation and figure dimension of draw-out type circuit breaker (Inm=3200A 3P 4P)
Dimension of panel hole see picture and table Unit:mm
Interlock device of circuit breaker see picture Unit:mm
Interlock device of vertical install circuit breaker
Interlock device of horizontal install circuit breaker
Characteristic of intelligent controller
|
Basic function |
| |
Overload longtime-delay/anti-time limit protection |
| Short circuit short time-delay/anti-time limit protection |
| Short circuit short time-delay timing protection |
| Short circuit instantaneous protection |
| Insulate earth fault protection |
| Display function |
|
|
| Current (select 1) |
Digital display |
Can display L1, L2, L3, ImaxI G(earth), IG(Neutral) |
| Voltage (select 2) |
Digital display |
Can display U12, U23, U31, Umin |
| Power (select 2) |
P |
| Power factor (select 2) |
|
COSΦ |
| Warning function |
|
|
| Over current fault warning |
Light-emitting diodes on panel |
After fault trip indicator light corresponding |
| Fault category identification |
Light-emitting diodes on panel |
Overload log time-delay |
|
Short circuit short time-delay |
| Short circuit instantaneous |
| Earth fault |
| Fault phase sequence |
Digital display |
Display the fault phase sequence |
| Current |
|
Breaking current |
| Time display |
|
Breaking time |
| Contact loss indication |
Digital display |
Display percentage of loss |
| Self-diagnosis function |
|
Send the error signal |
| Testing function |
|
|
| Panel key |
Tripping |
Test the time current characteristic of release and situation of operation device |
| Remote monitoring function |
Non-tripping |
Test the time current characteristic of release |
| Remote monitoring code signal optocoupler |
Relay (contain power) module |
Output of various working condittion |
| Communication function |
|
|
| Communicate type |
RS485(communication) I/O |
User should consult with the manufacturer |
Electrical accessories
| Under-voltage release |
Rated working voltage Ue(V) |
AC400 AC230 |
| |
Acting voltage (V) |
(0.35~0.7) Ue |
| Reliable close voltage (V) |
(0.85~1.1) Ue |
| Non close voltage (V) |
≤0.335Ue |
| Power loss |
12VA (YCW1-1000 5VA) |
| Shunt release |
Rated control power voltage Us(V) |
AC400 AC230 DC220 DC110 |
| |
Acting voltage (V) |
(0.7~1.1) Ue |
| Power loss |
40VA 40W (YCW1-1000 5VA) |
| Open time |
less than 30ms |
| Close electromagnetic iron |
Rated control power voltage Us(V) |
AC400 AC230 DC220 DC110 |
| |
Acting voltage (V) |
(0.85~1.1) Ue |
| Power loss |
40VA 40W (YCW1-1000 5VA) |
| Open time |
less than 70ms |
| Motor operating device |
Rated control power voltage Us(V) |
AC400 AC230 DC220 DC110 |
| |
Acting voltage (V) |
(0.85~1.1) Ue |
| Power loss |
40VA 40W (YCW1-1000 5VA) |
| Open time |
less than 5s |