16 Amp 2 Pole MCB

Selection

YCB7 - 63 N 1P C 16
Model Shell grade current Breaking capacity Number of poles Tripping
characteristics
Rated curren
Miniatur
circuit breaker
e
63 N:6kA 1P
2P
3P
4P
B
C
D
1
2
4
6
10
16
20
25
32
40
50
63

Note:This product can be assembled with accessories(YCB7-63N  OF/SD/OF+SD/ MX/ MVMN/MX+OF, etc)

Technical data

Type Standard   IEC/EN 60898-1
Comprehensive data Function   Overload, Short circuit, Isolation
Number of poles   1P,2P,3P,4P
Rated current In A 1-63A
Rated frequency Hz 50/60Hz
Electrical features Rated voltage Ue V 230/400
Rated insulation voltage Ui V 500
Rated breaking capacity Icn A 6000
Rated impulse withstand voltage Uimp(1.2/50) kA 4
Pollution degree   2
Use category   II、III
Trip type   Thermal magnetic release
Thermal magnetic tripping characteristics   B,C,D
Electrical and mechanical accessories  
Mechanical features Mechanical life Times 20000
Electrical life Times 10000
Protection degree   IP20
Antihumidity and heat resistance   The relative humidity of the air is not more than 50% when the ambient air temperature is +40°C, and it can have a higher relative humidity at a lower temperature
Reference ambient temperature °C 30
Ambient temperature °C -5°C-+40°C, the average value of 24h does not exceed +35°C
Height m Not exceeding 2000
Installation Terminal connection type   Cable/Pin-type busbar
Maximum
wire capacity
Terminal size mm² 25
top/bottom for cable AWG 18-3
Terminal size mm² 25
top/bottom for busbar AWG 18-3
Torque N*m 2
In-lbs 18
Tool 18 Phillips screwdriver or flat-blade screwdriver
Installation   On DIN rail EN 60715 (35mm) by means of fast clip device
Wiring method   From top or bottom

Overall and mounting dimensions(mm)

Selection

Type Test current Tripping time Expected result   Type Test current Tripping time Expected result
B,C,D 1.13In t≤1h(In≤63A) Not tripping B 3In t≤0.1s Not tripping
1.13In t≤2h(In>63A) C 5In t≤0.1s
B,C,D 1.45In t<1h(In≤63A) Tripping D 10In t≤0.1s
1.45In t<2h(In>63A) B 5In t<0.1s Tripping
B,C,D 2.55In 1s<t<60s(In≤32A) Tripping C 10In t<0.1s
2.55In 1s<t<120s(In>32A) D 20In t<0.1s

Curve

 FAQ

What is a 16 amp MCB used for?

Protects circuits/devices from overload/short circuits in AC 230V/400V systems, ideal for medium-low power loads like lighting, household appliances, and office equipment.

Why use a 2 pole MCB?

Cuts both live and neutral wires simultaneously for full isolation, enhancing safety during maintenance. Suitable for 230V single-phase circuits (e.g., air conditioners, water heaters).

How much load can a 16 amp MCB take?

Up to ~3,680W (16A×230V) for resistive loads (e.g., heaters); derate to ~3,000W for inductive loads (e.g., motors) for stability.

Which MCB is best, B or C?

B-type: Trips at 3-5×In (low inrush loads: lighting, sockets).

C-type: Trips at 5-10×In (medium inrush loads: motors, pumps). Choose based on load type.