AFDD9NL-40 AFDD RCBO Arc Fault Detection Device 1P+N

General

The AFDD9NL-40 series Arc Fault Detection Device are assembled from 18mm - wide double - pole leakage circuit breakers (RCBO) and arc - detection modules. The products have functions of short - circuit protection, over - current protection, over - voltage protection, leakage protection, and arc - fault protection. The AFDD9NL-40 series Arc Fault Detection Device meet the performance requirements of the standard IEC62606 - 2013. The AFDD9NL-40 series is designed in particular for UK market.  

Type designation

AFDD9NL-40 offers maximum protection against:

  • Series arc faults
  • Short circuits
  • Parallel arc faults
  • Overloads
  • Earth arc faults
  • Over - voltage Protection
  • Earth leakge faults

LED Indication

LED illumination for AFDD operation and arc fault identification 1. LED flashes in RED for 5 times when AFDD is re-closed after tripping, the tripping is caused arc fault. 2. LED flashes in YELLOW for 3 times as one cycle and such cycle repeats for 5 times when AFDD is re-closed after tripping, the tripping is caused by earth leakage fault. 3. LED flashes in YELLOW for 2 times as one cycle and such cycle repeats for 5 times when AFDD is re-closed after tripping, the tripping is caused by over-voltage. 4. LED turns GREEN when AFDD is re-closed after tripping, the tripping is caused by either overload or short circuit. 5. LED flashes in RED, AFDD is operating improperly and shall be replaced by professionals.

Tripping curves

 

 

Technical data

Content Technical data
Rated voltage Ue,V AC230/240
Approvals CE
Rated frequency,Hz 50 
Rated insulation voltage Ui,V 500 
Rated impulse withstand voltage Uimp,V 4000 
Rated current In,A 6,10,16,20,25,32,40
Number of poles 1P+N
Instantaneous tripping type B,C
Sensitivity I△n,mA 30 
RCD type AC,A
Rated short circuit breaking capacity Icn,A 6000 
Mechanical and electrical endurance,cycles 4000 
Protection degree IP20
Ambient temperature,℃ -25~+40
Standards IEC62606,IEC61009-1

 

Overall and mounting dimensions(mm)

Ordering references

 

References Pole No. Rated current
In,A
Sensitivity
I△n,mA
Tripping
curve
RCD
type
AFDD9NL-401P+N B6 Type AC 1P+N 30mA B AC
AFDD9NL-401P+N B10 Type AC 1P+N 10  30mA B AC
AFDD9NL-401P+N B16 Type AC 1P+N 16  30mA B AC
AFDD9NL-401P+N B20 Type AC 1P+N 20  30mA B AC
AFDD9NL-401P+N B25 Type AC 1P+N 25  30mA B AC
AFDD9NL-401P+N B32 Type AC 1P+N 32  30mA B AC
AFDD9NL-401P+N B40 Type AC 1P+N 40  30mA B AC
AFDD9NL-401P+N B6 Type A 1P+N 30mA B A
AFDD9NL-401P+N B10 Type A 1P+N 10  30mA B A
AFDD9NL-401P+N B16 Type A 1P+N 16  30mA B A
AFDD9NL-401P+N B20 Type A 1P+N 20  30mA B A
AFDD9NL-401P+N B25 Type A 1P+N 25  30mA B A
AFDD9NL-401P+N B32 Type A 1P+N 32  30mA B A
AFDD9NL-401P+N B40 Type A 1P+N 40  30mA B A
AFDD9NL-401P+N C6 Type AC 1P+N 30mA C AC
AFDD9NL-401P+N C10 Type AC 1P+N 10  30mA C AC
AFDD9NL-401P+N C16 Type AC 1P+N 16  30mA C AC
AFDD9NL-401P+N C20 Type AC 1P+N 20  30mA C AC
AFDD9NL-401P+N C25 Type AC 1P+N 25  30mA C AC
AFDD9NL-401P+N C32 Type AC 1P+N 32  30mA C AC
AFDD9NL-401P+N C40 Type AC 1P+N 40  30mA C AC
AFDD9NL-401P+N C6 Type A 1P+N 30mA C A
AFDD9NL-401P+N C10 Type A 1P+N 10  30mA C A
AFDD9NL-401P+N C16 Type A 1P+N 16  30mA C A
AFDD9NL-401P+N C20 Type A 1P+N 20  30mA C A
AFDD9NL-401P+N C25 Type A 1P+N 25  30mA C A
AFDD9NL-401P+N C32 Type A 1P+N 32  30mA C A
AFDD9NL-401P+N C40 Type A 1P+N 40  30mA C A

AFDD9NL-40 FAQ

Frequently asked questions about AFDD9NL-40 Arc Fault Detection Device for final distribution and branch circuit protection.

1. What is AFDD9NL-40?

AFDD9NL-40 is an Arc Fault Detection Device assembled from an 18mm-wide double-pole RCBO and an arc-detection module. It is designed for branch circuits to improve electrical safety in final distribution.

2. What protection functions does AFDD9NL-40 provide?

AFDD9NL-40 provides arc-fault protection, leakage (residual current) protection, short-circuit protection, over-current/overload protection, and over-voltage protection.

3. What types of arc faults can AFDD9NL-40 detect?

AFDD9NL-40 offers protection against series arc faults, parallel arc faults, and earth arc faults, helping reduce the risk of electrical fires caused by arcing.

4. Does AFDD9NL-40 also protect against earth leakage faults?

Yes. AFDD9NL-40 integrates RCBO functions, providing leakage protection and a built-in RCD test button to verify residual current operation.

5. What is the rated voltage and frequency of AFDD9NL-40?

AFDD9NL-40 is rated for AC 230/240 V and 50 Hz operation.

6. What rated current options are available?

AFDD9NL-40 is available in 6A, 10A, 16A, 20A, 25A, 32A, and 40A rated current options.

7. What poles, tripping curves, and leakage sensitivity does AFDD9NL-40 support?

AFDD9NL-40 is 1P+N. It supports B and C tripping curves and a leakage sensitivity of 30 mA.

8. What RCD types are available for AFDD9NL-40?

AFDD9NL-40 is available with RCD type AC or type A, depending on the application requirements.

9. What does the LED indication mean on AFDD9NL-40?

The AFDD LED provides status and fault identification: it flashes red for arc-fault trips, flashes yellow for earth leakage or over-voltage related trips (different flash patterns), and turns green when re-closed after overload or short-circuit trips. A red flashing LED can also indicate abnormal operation and the device should be replaced by professionals.

10. What standards does AFDD9NL-40 comply with, and which market is it designed for?

AFDD9NL-40 meets IEC 62606 (2013 performance requirements) and references IEC 61009-1. It is designed in particular for the UK market.