CJX2s-M Series AC Contactor by
cncelectric on
Sketchfab
Product Overview
CJX2s-M series AC Contactor with novel appearance and compact structure is suitable for using starting & controlling the AC motor frequently, switching on and off the circuit at a long distance. It is used in combination with thermal relay to compose a magnetic motor starter.
Standard: IEC 60947-1, IEC 60947-4-1.
Model and Meaning
Specifications
Rated operation current(Ie): 6-16A;
Rated operation voltage(Ue): 220V~690V;
Rated insulation voltage: 690V;
Poles: 3P、4P;
Installation: Din rail and screw installation
Type |
Operating and Installation Conditions |
Installation category |
III |
Pollution level |
3 |
Certification |
CE, CB, CCC, TUV |
Protection degree |
Ip20 |
Ambient temperature |
limit of temperature: -35℃~+70℃,normal temperature: -5℃~+40℃,The average no more than +35℃ within 24 hours.If not in normal operating temperature range, please refer to "Instructions for abnormal environment" |
Altitude |
≤2000m |
Ambient temperature |
The maximum temperature of 70 degrees, the air relative humidity not exceed 50%, under lowertemperature can allow for higher relative humidity.If the temperature is 20℃, the air relative humiditycould up to 90%, Special measures should betakenfor occasional condensation dueto humidity changes. |
Installation position |
Inclination between installation surface and vertical surface should not exceed ±5° |
Shock vibration |
Products should be installed and used withoutsignificant shake, shock and vibration place. |
Appearance
|
|
Type |
CJX2s-M06 |
CJX2s-M09 |
CJX2s-M12 |
CJX2s-M16 |
Poles |
3P/4P |
Rated insulation voltage(Ui) |
V |
690 |
Rated operating voltage(Ue) |
V |
380/400, 660/690 |
Rated thermal current(Ith) ,AC-1 |
20 |
Ratedoperation current(Ie) |
AC-3,380/400V |
A |
6 |
9 |
12 |
16 |
AC-3,660/690V |
A |
3.8 |
4.9 |
4.9 |
4.9 |
AC-4,380/400V |
A |
6 |
9 |
9 |
12 |
AC-4,660/690V |
A |
3.8 |
4.9 |
4.9 |
4.9 |
Rated operational power(Pe) |
AC-3,380/400V |
kW |
2.2 |
4 |
5.5 |
7.5 |
AC-3,660/690V |
kW |
3 |
4 |
4 |
4 |
Mechanical life |
|
10000 times |
1200 |
Electrical life |
AC-3 |
120 |
AC-4 |
|
See electrical life curve |
Frequencyof operation |
AC-3 |
times/ hour |
1200 |
AC-4 |
300 |
Flexible wire |
1 wire mm² |
1…4 |
No terminal |
2 wire |
mm² |
1…4 |
Flexible wire |
1 wire |
mm² |
1…4 |
With terminals |
2 wire |
mm² |
1…2.5 |
Hard wire |
1 wire |
mm² |
1…4 |
No terminal |
2 wire |
mm² |
1…4 |
Fastening torque |
N·m |
1.2 |
Coil |
Rated control voltage(Us) |
50Hz |
V |
24、36、48、110、127、220、380、415 |
50/60Hz |
V |
24、36、48、110、127、220、380、415 |
DC |
V |
12、24、36、48、110、127、220 |
Allowed control circuit voltage(Us) |
Operation |
V |
Installation inclination angle ±22.5°: 85%~110%Us; Installation inclination angle±5°: 70%~120% |
Release(AC) |
V |
Installation inclination angle ±22.5°: 20%~75%Us;Installation inclination angle±5°: 20%~60% |
Release(DC) |
V |
Installation inclination angle ±22.5°: 10%~75%Us;Installation inclination angle±5°: 10%~60% |
Power consumption of coil |
Actuation |
VA |
20-40 |
Keep |
VA |
9.5 |
Consumption
|
W |
1-3 |
Auxiliary contacts specification |
A |
1NO/1NC |
Rated thermal current (Ith) |
A |
10 |
Rated operating voltage (Ue) |
AC |
V |
380/400 |
DC |
V |
220 |
Rated control capacit |
AC-15 |
VA |
Ue/Ie: AC380V/400V/ 1. 5A It h: 10A |
DC-13 |
W |
Ue/Ie: DC220V/0. 3A |
Overall and Mounting
Type |
Amax |
Bmax |
Cmax |
Dmax |
a |
b |
Φ |
CJX2s-M06-M16 |
45.5 |
59 |
58 |
94 |
35±0.35 |
50±0.48 |
4.2 |
CJX2s-M06/Z-M16/Z
|
45.5 |
59 |
70 |
106 |
35±0.35 |
50±0.48 |
4.2 |
Type |
Amax |
Bmax |
Cmax |
Dmax |
a |
b |
Φ |
CJX2s-M06/N-M16/N |
91 |
59 |
58 |
94 |
80±0.35 |
50±0.48 |
4.2 |
CJX2s-M06/Z/N-M16/Z/N |
91 |
59 |
70 |
106 |
35±0.35 |
50±0.48 |
4.2 |
CJX2s-M AC Contactor selection table
Motor power kW |
Maximum operation current A |
Number of contacts contained in the contactor body |
Contactor model |
380V/400V |
660V/690V |
(AC-3 380V/400V) |
NO |
NC |
2.2 |
3 |
6 |
1 |
0 |
CJX2s-M0610 |
2.2 |
3 |
6 |
0 |
1 |
CJX2s-M0601 |
2.2 |
3 |
6 |
0 |
0 |
CJX2s-M0604 |
2.2 |
3 |
6 |
0 |
0 |
CJX2s-M0608 |
4 |
4 |
9 |
1 |
0 |
CJX2s-M0910 |
4 |
4 |
9 |
0 |
1 |
CJX2s-M0901 |
4 |
4 |
9 |
0 |
0 |
CJX2s-M0904 |
4 |
4 |
9 |
0 |
0 |
CJX2s-M0908 |
5.5 |
4 |
12 |
1 |
0 |
CJX2s-M1210 |
5.5 |
4 |
12 |
0 |
1 |
CJX2s-M1201 |
5.5 |
4 |
12 |
0 |
0 |
CJX2s-M1204 |
5.5 |
4 |
12 |
0 |
0 |
CJX2s-M1208 |
7.5 |
4 |
16 |
1 |
0 |
CJX2s-M1610 |
7.5 |
4 |
16 |
0 |
1 |
CJX2s-M1601 |
7.5 |
4 |
16 |
0 |
0 |
CJX2s-M1604 |
7.5 |
4 |
16 |
0 |
0 |
CJX2s-M1608 |
CJX2s-MAC Contactor Coil voltage specification table
AC(V) 50Hz |
24 |
36 |
48 |
110 |
127 |
220 |
380 |
415 |
AC(V) 60Hz |
24 |
36 |
48 |
110 |
127 |
220 |
380 |
415 |
AC(V) 50/60Hz |
24 |
36 |
48 |
110 |
127 |
220 |
380 |
415 |
DC(V) |
12 |
24 |
36 |
48 |
110 |
127 |
220 |
- |
Instructions for use of correction factors in high altitude areas
Altitude (m) |
2000 |
3000 |
4000 |
Rated impulse withstand voltage correction factor |
1 |
0.88 |
0.78 |
Rated operation current correction factor |
1 |
0.92 |
|
Instructions for use under abnormal ambient temperature
Ambient temperature (℃) |
55 |
60 |
65 |
70 |
Correction factor |
1 |
0.93 |
0.875 |
0.75 |