DR-30W
Single output: power 30W
Input voltage: 85~264VAC 120~370VDC
| Model Specification |
DR-30-12 | DR-30-24 |
| DC output voltage, current | 12V 0~2A | 24V 0~1.5A |
| Wave and noise | 120mVp-p | 150mVp-p |
| Inlet wire stability | ±0.5% | ±0.5% |
| Load stability | ±0.5% | ±0.5% |
| Efficiency | 81% | 83% |
| Adjustable range for DC voltage | ±10% | ±10% |
| Input voltage range | 85~264VAC 120~370VDC 47-63Hz | |
| Impact current | Cold start current 15A/115VAC 30A/230VAC | |
| Overload protection | 105%~160% cut off the output, automtic recovery | |
| Over voltage protection | 115%-135% shutdownO/Pvoltage, re-poweronto recover | |
| Setup, rise, hold up time | 800ms, 60ms, 50ms/230VAC at full load | |
| Withstand voltage | I/P-O/P: 1.5kV I/P-FG: 1.5kV O/P-FG: 0.5kV 1minute | |
| Isolation resistance | I/P-O/P I/P-FG O/P-F/G: 500VDC/100MΩ | |
| Working temperature | -10℃~+50℃ | |
| Dimension | 78×93×56mm | |
DR-45W
Single output: power 45W
Input voltage: 85~264VAC 120~370VDC
| Model Specification |
DR-45-12 | DR-45-24 |
| DC output voltage, current | 12V 0~3.5A | 24V 0~2A |
| Wave and noise | 120mVp-p | 150mVp-p |
| Inlet wire stability | ±0.5% | ±0.5% |
| Load stability | ±0.5% | ±0.5% |
| Efficiency | 77% | 80% |
| Adjustable range for DC voltage | ±10% | ±10% |
| Input voltage range | 85~264VAC 120~370VDC 47-63Hz | |
| Impact current | Cold start current 28A/115VAC 56A/230VAC | |
| Overload protection | 105%~150% cut off the output, automtic recovery | |
| Over voltage protection | 115%-135% shutdownO/Pvoltage, re-poweronto recover | |
| Setup, rise, hold up time | 800ms, 60ms, 50ms/230VAC at full load | |
| Withstand voltage | I/P-O/P: 1.5kV I/P-FG: 1.5kV O/P-FG: 0.5kV 1minute | |
| Isolation resistance | I/P-O/P I/P-FG O/P-F/G: 500VDC/100MΩ | |
| Working temperature | -10℃~+50℃ | |
| Dimension | 78×93×56mm | |
DR-60W
Single output: power 60W
Input voltage: 85~264VAC 120~370VDC
| Model Specification |
DR-60-12 | DR-60-24 |
| DC output voltage, current | 12V 0~4.5A | 24V 0~2.5A |
| Wave and noise | 120mVp-p | 150mVp-p |
| Inlet wire stability | ±0.5% | ±0.5% |
| Load stability | ±0.5% | ±0.5% |
| Efficiency | 82% | 84% |
| Adjustable range for DC voltage | ±10% | ±10% |
| Input voltage range | 85~264VAC 120~370VDC 47-63Hz | |
| Impact current | Cold start current 18A/115VAC 36A/230VAC | |
| Overload protection | 105%~160% cut off the output, automtic recovery | |
| Over voltage protection | 115%-135% shutdownO/Pvoltage, re-poweronto recover | |
| Setup, rise, hold up time | 800ms, 60ms, 50ms/230VAC at full load | |
| Withstand voltage | I/P-O/P: 1.5kV I/P-FG: 1.5kV O/P-FG: 0.5kV 1minute | |
| Isolation resistance | I/P-O/P I/P-FG O/P-F/G: 500VDC/100MΩ | |
| Working temperature | -10℃~+50℃ | |
| Dimension | 78×93×56mm | |