JD-8 Motor Integrated Protector

Operating conditions

  • The altitude shall not exceed 2000m.
  • The ambient air temperature is -5℃~+40℃ and the average temperature within 24h shall not exceed +35℃.
  • Atmospheric condition: Relative humidity of atmosphere shall not exceed 50% at the temperature of +40℃,and higher relative humidity is allowed at lower temperature. For example, the air humidity can reach 90% at the temperature of +20℃. Regarding the condensation casually caused by humidity change, special measures shall be taken.
  • Class of pollution: Class III
  • Installation category: category III
  • The angle between the installation surface and the vertical surface shall not exceed ±5 degrees.
  • The place without obvious shake, impact and vibration shall be selected as the installation site.
  • The installation site shall conform to the following standards: explosive and dangerous medium, no gas capable of corroding and damaging insulation in the medium and less conductive dust in the medium.
  • The place with rain-proof and snow-proof equipment and a little water vapor shall be used as the installation site

Technical data

Main circuit: rated insulation voltage AC690V, rated frequency 50Hz

Others

Model    Range of setting
current (A)
    Power suitable
for motor (kW)
JD-8 0.5~5 0.25~2.5
2~20 1~10
20~80 10~40
64~160 32~80

 

Auxiliary circuit: rated insulation voltage AC380V, rated frequency 50Hz

Utility Category AC-15
Rated operating voltage (V) 220 380
Rated operating current (A) 1.5 0.95
Conventional thermal current (A) 5

Structure characteristics
●Three-phase electronic type
●Function of phase failure and overload protection(not suitable for reversible motor)
●Device capable of continuously adjusting setting current
●The main circuit adopts pass-through-core type wiring method
●Installation method: installation via screws or rail
The protector has the following operating characteristics for load balance of each phase; the tripping level is level 30.

Multiple of setting current Actuation time Starting condition Ambient air temperature
1.05 No actuation within 2h Cold state Room temperature
(20±5)℃
1.2 Actuation within 2h     Heat state (the test is done
following sequence 1)
1.5 Actuation within 12min
7.2 9s<tp≤30s Cold state