The S□ -M series three-phase oil-immersed transformer adopts a fully oil-filled, sealed corrugated oil tank. and the oil tank shell adapts to the expansion performance of the oil with its own elasticity and meets the heat dissipation requirements. It has the characteristics of high efficiency and low loss, which
can save a lot of power consumption and operating costs, and is widely used in power plants, substations, industrial and mining enterprises, ports, airports and other environmental protection places.
Standard: IEC60076-1, IEC60076-2, IEC60076-3, IEC60076-5, IEC60076-10.
1. Ambient temperature: maximum temperature: +40°C, minimum temperature: -25℃ .
2. Average temperature of the hottest month:+30℃, average temperature in the hottest year: +20℃ .
3. Altitude not exceeding 1000m.
4. The waveform of the power supply voltage is similar to a sine wave.
5. The three-phase supply voltage should be approximately symmetrical.
6. The total harmonic content of the load current shall not exceed 5% of the rated current.
7. Where to use: indoors or outdoors.
1. The product has the characteristics of high efficiency, low loss, low noise, etc.
2. High mechanical strength, balanced ampere-turn distribution, and strong short-circuit resistance.
3. Low no-load and load loss.
4. Small size, reliable operation, long service life, and maintenance free.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
130 | 630/600 | 2.3 | 4 | 745 | 530 | 890 | 280 |
50 | 170 | 910/870 | 2 | 790 | 560 | 940 | 365 | |||||
63 | 200 | 1090/1040 | 1.9 | 820 | 570 | 950 | 425 | |||||
80 | 250 | 1310/1250 | 1.9 | 850 | 580 | 1000 | 485 | |||||
100 | 290 | 1580/1500 | 1.8 | 900 | 620 | 1010 | 540 | |||||
125 | 340 | 1890/1800 | 1.7 | 880 | 630 | 1050 | 610 | |||||
160 | 400 | 2310/2200 | 1.6 | 950 | 690 | 1120 | 710 | |||||
200 | 480 | 2730/2600 | 1.5 | 990 | 730 | 1200 | 835 | |||||
250 | 560 | 3200/3050 | 1.4 | 1180 | 700 | 1200 | 970 | |||||
315 | 670 | 3830/3650 | 1.4 | 1230 | 760 | 1250 | 1125 | |||||
400 | 800 | 4520/4300 | 1.3 | 1260 | 800 | 1300 | 1310 | |||||
500 | 960 | 5410/5150 | 1.2 | 1400 | 900 | 1320 | 1530 | |||||
630 | Dyn11 Yyn0 Yzn11 |
1200 | 6200 | 1.1 | 4.5 | 1530 | 940 | 1350 | 1890 | |||
800 | 1400 | 7500 | 1 | 1580 | 1000 | 1420 | 2185 | |||||
1000 | 1700 | 10300 | 1 | 1770 | 1180 | 1450 | 2480 | |||||
1250 | 1950 | 12000 | 0.9 | 1920 | 1290 | 1430 | 3020 | |||||
1600 | 2400 | 14500 | 0.8 | 1990 | 1340 | 1620 | 3550 | |||||
2000 | 3000 | 17100 | 0.7 | 5 | 1950 | 1680 | 2100 | 4530 | ||||
2500 | 3300 | 23200 | 0.7 | 2020 | 1710 | 2100 | 5030 |
Note 1:for transformers with rated capacity of 500kVA and below, the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group,and the load loss values below the diagonal line are applicable to the Yyn0 coupling group.
Note 2:when the average annual load rate of the transformer is between 35% and 40%, the maximum operating eficiency can be obtained by using the loss value in the table.
Note:The dimensions and weights provided are only for reference in design and selection.The final size and weight are subject to our product drawings.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
100 | 630/600 | 1.5 | 4 | 690 | 510 | 920 | 275 |
50 | 130 | 910/870 | 1.3 | 730 | 510 | 960 | 340 | |||||
63 | 150 | 1090/1040 | 1.2 | 750 | 550 | 1000 | 385 | |||||
80 | 180 | 1310/1250 | 1.2 | 790 | 620 | 1020 | 450 | |||||
100 | 200 | 1580/1500 | 1.1 | 790 | 700 | 1040 | 520 | |||||
125 | 240 | 1890/1800 | 1.1 | 840 | 800 | 1070 | 625 | |||||
160 | 280 | 2310/2200 | 1 | 1070 | 670 | 1130 | 695 | |||||
200 | 340 | 2730/2600 | 1 | 1140 | 750 | 1140 | 795 | |||||
250 | 400 | 3200/3050 | 0.9 | 1200 | 800 | 1190 | 955 | |||||
315 | 480 | 3830/3650 | 0.9 | 1300 | 860 | 1210 | 1085 | |||||
400 | 570 | 4520/4300 | 0.8 | 1380 | 900 | 1240 | 1290 | |||||
500 | 680 | 5410/5100 | 0.8 | 1450 | 950 | 1300 | 1590 | |||||
630 | Dyn11 Yyn0 Yzn11 |
810 | 6200 | 0.6 | 4.5 | 1500 | 970 | 1360 | 1850 | |||
800 | 980 | 7500 | 0.6 | 1660 | 1140 | 1400 | 2210 | |||||
1000 | 1150 | 10300 | 0.6 | 1690 | 1190 | 1530 | 2570 | |||||
1250 | 1360 | 12000 | 0.5 | 1760 | 1230 | 1600 | 3115 | |||||
1600 | 1640 | 14500 | 0.5 | 1800 | 1250 | 1660 | 3520 | |||||
2000 | 1940 | 18300 | 0.4 | 5 | 1930 | 1360 | 1490 | 4060 | ||||
2500 | 2290 | 21200 | 0.4 | 2080 | 1360 | 1570 | 5105 |
Note 1:for transformers with rated capacity of 500kVA and below, the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group,and the load loss values below the diagonal line are applicable to the Yyn0 coupling group.
Note 2:when the average annual load rate of the transformer is between 35% and 40%, the maximum operating eficiency can be obtained by using the loss value in the table.
Note:The dimensions and weights provided are only for reference in design and selection.The final size and weight are subject to our product drawings.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
80 | 630/600 | 1.5 | 4 | 685 | 490 | 860 | 260 |
50 | 100 | 910/870 | 1.3 | 725 | 520 | 955 | 365 | |||||
63 | 110 | 1090/1040 | 1.2 | 750 | 535 | 970 | 415 | |||||
80 | 130 | 1310/1250 | 1.2 | 770 | 565 | 985 | 465 | |||||
100 | 150 | 1580/1500 | 1.2 | 800 | 595 | 1000 | 545 | |||||
125 | 170 | 1890/1800 | 1.1 | 815 | 670 | 1010 | 585 | |||||
160 | 200 | 2310/2200 | 1.1 | 1015 | 645 | 1055 | 695 | |||||
200 | 240 | 2730/2600 | 1 | 1020 | 650 | 1115 | 810 | |||||
250 | 290 | 3200/3050 | 1 | 1140 | 730 | 1120 | 930 | |||||
315 | 340 | 3830/3650 | 0.9 | 1195 | 785 | 1175 | 1075 | |||||
400 | 410 | 4520/4300 | 0.9 | 1265 | 855 | 1195 | 1255 | |||||
500 | 480 | 5410/5100 | 0.8 | 1325 | 915 | 1240 | 1435 | |||||
630 | Dyn11 Yyn0 Yzn11 |
570 | 6200 | 0.8 | 4.5 | 1465 | 960 | 1295 | 1880 | |||
800 | 700 | 7500 | 0.6 | 1515 | 995 | 1340 | 2145 | |||||
1000 | 830 | 10300 | 0.6 | 1605 | 1095 | 1460 | 2455 | |||||
1250 | 970 | 12000 | 0.5 | 1685 | 1145 | 1485 | 2840 | |||||
1600 | 1170 | 14500 | 0.5 | 1775 | 1225 | 1580 | 3310 | |||||
2000 | 1550 | 18300 | 0.4 | 5 | 1855 | 1265 | 1600 | 3960 | ||||
2500 | 1830 | 21200 | 0.4 | 1885 | 1305 | 1780 | 4980 |
Note 1:for transformers with rated capacity of 500kVA and below, the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group,and the load loss values below the diagonal line are applicable to the Yyn0 coupling group.
Note 2:when the average annual load rate of the transformer is between 35% and 40%, the maximum operating eficiency can be obtained by using the loss value in the table.
Note:The dimensions and weights provided are only for reference in design and selection.The final size and weight are subject to our product drawings.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Yzn11 |
80 | 505/480 | 1.5 | 4 | 785 | 710 | 880 | 370 |
50 | 100 | 730/695 | 1.3 | 800 | 730 | 940 | 480 | |||||
63 | 110 | 870/830 | 1.2 | 815 | 720 | 970 | 535 | |||||
80 | 130 | 1050/1000 | 1.2 | 830 | 740 | 990 | 580 | |||||
100 | 150 | 1260/1200 | 1.1 | 875 | 790 | 1010 | 705 | |||||
125 | 170 | 1510/1440 | 1.1 | 875 | 770 | 1050 | 775 | |||||
160 | 200 | 1850/1760 | 1 | 935 | 820 | 1140 | 975 | |||||
200 | 240 | 2180/2080 | 1 | 995 | 870 | 1140 | 1140 | |||||
250 | 290 | 2560/2440 | 0.9 | 995 | 900 | 1180 | 1240 | |||||
315 | 340 | 3060/2920 | 0.9 | 1030 | 880 | 1250 | 1425 | |||||
400 | 410 | 3610/3440 | 0.8 | 1075 | 910 | 1270 | 1635 | |||||
500 | 480 | 4330/4120 | 0.8 | 1120 | 930 | 1320 | 1950 | |||||
630 | Dyn11 Yyn0 Yzn11 |
570 | 4960 | 0.6 | 4.5 | 1165 | 950 | 1350 | 2150 | |||
800 | 700 | 6000 | 0.6 | 1210 | 1050 | 1390 | 2515 | |||||
1000 | 830 | 8240 | 0.6 | 1520 | 1020 | 1450 | 2635 | |||||
1250 | 970 | 9600 | 0.5 | 1630 | 1090 | 1540 | 3210 | |||||
1600 | 1170 | 11600 | 0.5 | 1680 | 1150 | 1600 | 3905 | |||||
2000 | 1550 | 14600 | 0.4 | 5 | 1890 | 1300 | 1600 | 4130 | ||||
2500 | 1830 | 16900 | 0.4 | 1990 | 1360 | 1700 | 5250 |
Note 1:for transformers with rated capacity of 500kVA and below, the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group,and the load loss values below the diagonal line are applicable to the Yyn0 coupling group.
Note 2:when the average annual load rate of the transformer is between 35% and 40%, the maximum operating eficiency can be obtained by using the loss value in the table.
Note:The dimensions and weights provided are only for reference in design and selection.The final size and weight are subject to our product drawings.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
70 | 505 | 1.2 | 4 | 785 | 710 | 880 | / |
50 | 90 | 730 | 1.04 | 800 | 730 | 940 | / | |||||
80 | 115 | 1050 | 0.96 | 830 | 740 | 990 | / | |||||
100 | 135 | 1265 | 0.88 | 875 | 790 | 1010 | / | |||||
125 | 150 | 1510 | 0.88 | 875 | 770 | 1050 | / | |||||
160 | 180 | 1850 | 0.8 | 935 | 820 | 1140 | / | |||||
200 | 215 | 2185 | 0.8 | 995 | 870 | 1140 | / | |||||
250 | 260 | 2560 | 0.72 | 995 | 900 | 1180 | / | |||||
315 | 305 | 3065 | 0.72 | 1030 | 880 | 1250 | / | |||||
400 | 370 | 3615 | 0.64 | 1075 | 910 | 1270 | / | |||||
500 | 430 | 4330 | 0.64 | 1120 | 930 | 1320 | / | |||||
630 | 510 | 4960 | 0.48 | 4.5 | 1165 | 950 | 1350 | / | ||||
800 | 630 | 6000 | 0.48 | 1210 | 1050 | 1390 | / | |||||
1000 | 745 | 8240 | 0.48 | 1520 | 1020 | 1450 | / | |||||
1250 | 870 | 9600 | 0.4 | 1630 | 1090 | 1540 | / | |||||
1600 | 1050 | 11600 | 0.4 | 1680 | 1150 | 1600 | / | |||||
2000 | 1225 | 14640 | 0.32 | 5 | 1890 | 1300 | 1600 | / | ||||
2500 | 1440 | 14840 | 0.32 | 1990 | 1360 | 1700 | / |
Note 1:for transformers with rated capacity of 500kVA and below, the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group,and the load loss values below the diagonal line are applicable to the Yyn0 coupling group.
Note 2:when the average annual load rate of the transformer is between 35% and 40%, the maximum operating eficiency can be obtained by using the loss value in the table.
Note:The dimensions and weights provided are only for reference in design and selection.The final size and weight are subject to our product drawings
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
30 | 6 6.3 10 10.5 11 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
65 | 455 | 1.2 | 4 | 785 | 710 | 880 | / |
50 | 80 | 655 | 1.04 | 800 | 730 | 940 | / | |||||
80 | 105 | 945 | 0.96 | 830 | 740 | 990 | / | |||||
100 | 120 | 1140 | 0.88 | 875 | 790 | 1010 | / | |||||
125 | 135 | 1360 | 0.88 | 875 | 770 | 1050 | / | |||||
160 | 160 | 1665 | 0.8 | 935 | 820 | 1140 | / | |||||
200 | 190 | 1970 | 0.8 | 995 | 870 | 1140 | / | |||||
250 | 230 | 2300 | 0.72 | 995 | 900 | 1180 | / | |||||
315 | 270 | 2760 | 0.72 | 1030 | 880 | 1250 | / | |||||
400 | 330 | 3250 | 0.64 | 1075 | 910 | 1270 | / | |||||
500 | 385 | 3900 | 0.64 | 1120 | 930 | 1320 | / | |||||
630 | 460 | 4460 | 0.48 | 4.5 | 1165 | 950 | 1350 | / | ||||
800 | 560 | 5400 | 0.48 | 1210 | 1050 | 1390 | / | |||||
1000 | 665 | 7415 | 0.48 | 1520 | 1020 | 1450 | / | |||||
1250 | 780 | 8640 | 0.4 | 1630 | 1090 | 1540 | / | |||||
1600 | 940 | 10440 | 0.4 | 1680 | 1150 | 1600 | / | |||||
2000 | 1085 | 13180 | 0.32 | 5 | 1890 | 1300 | 1600 | / | ||||
2500 | 1280 | 13360 | 0.32 | 1990 | 1360 | 1700 | / |
Note 1:for transformers with rated capacity of 500kVA and below, the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group,and the load loss values below the diagonal line are applicable to the Yyn0 coupling group.
Note 2:when the average annual load rate of the transformer is between 35% and 40%, the maximum operating eficiency can be obtained by using the loss value in the table.
Note:The dimensions and weights provided are only for reference in design and selection.The final size and weight are subject to our product drawings.
Rated capacity (KVA) |
Voltage combination | Connection group label | No-load loss(W) | Load loss(W) | No-load current (%) |
Short circuit impedance (%) |
Dimensions | Total weight (kg) |
||||
High voltage (KV) |
Tapping range |
Low voltage (KV) |
L | W | H | |||||||
25 | 20 10 6 |
±5 ±2 ×2.5 |
0.4 | Dyn11 Yyn0 Dyn5 |
63 | 600 | 1.7 | 5.5(20kV) 4 (6kV, 10kV) |
1090 | 600 | 1150 | / |
50 | 81 | 750 | 1.6 | 1120 | 620 | 1180 | / | |||||
100 | 130 | 1250 | 1.3 | 1150 | 650 | 1290 | / | |||||
160 | 189 | 1750 | 1.1 | 1160 | 675 | 1380 | / | |||||
250 | 270 | 2350 | 0.96 | 1200 | 880 | 1400 | / | |||||
315 | 324 | 2800 | 0.88 | 1230 | 920 | 1460 | / | |||||
400 | 387 | 3250 | 0.8 | 1250 | 950 | 1580 | / | |||||
500 | 459 | 3900 | 0.8 | 1390 | 960 | 1580 | / | |||||
630 | 540 | 4600 | 0.72 | 6(20kV) 4.5 (6kV, 10kV) |
1450 | 980 | 1600 | / | ||||
800 | 585 | 6000 | 0.64 | 1560 | 1020 | 1720 | / | |||||
1000 | 693 | 7600 | 0.56 | 1700 | 1070 | 1790 | / | |||||
1250 | 855 | 9500 | 0.56 | 1700 | 1070 | 1791 | / | |||||
1600 | 1080 | 12000 | 0.48 | 1850 | 1130 | 1850 | / | |||||
2000 | 1305 | 15000 | 0.48 | 6(20kV) 5 (6kV, 10kV) |
2000 | 1280 | 1980 | / | ||||
2500 | 1575 | 18500 | 0.4 | 2040 | 1320 | 2050 | / | |||||
3150 | 1980 | 23000 | 0.4 | 2200 | 1400 | 2250 | / |
Note 1:for transformers with rated capacity of 500kVA and below, the load loss values above the diagonal line in the table are applicable to the Dyn11 or Yzn11 coupling group,and the load loss values below the diagonal line are applicable to the Yyn0 coupling group.
Note 2:when the average annual load rate of the transformer is between 35% and 40%, the maximum operating eficiency can be obtained by using the loss value in the table.
Note:The dimensions and weights provided are only for reference in design and selection.The final size and weight are subject to our product drawings.