Type | XJ3-D |
Protection function | Overvoltage Undervoltage Phase-failure Phase-sequence error |
Overvoltage protection(AC) | 380V~460V 1.5s~4s (adjustable) |
Undervoltage protection(AC) | 300V~380V 2s~9s(adjustable) |
Operating voltage | AC 380V 50/60Hz |
Contact number | 1 group changeover |
Contact capacity | Ue/Ie:AC-15 380V/0.47A; Ith:3A |
Phase-failure and phase-sequence protection | Reacting time ≤2s |
Electrical life | 1×105 |
Mechanical life | 1×106 |
Ambient temperature | -5℃~40℃ |
Installation mode | 35mm Track installation or soleplate mounting |
Note: In the example diagram of the application circuit, the protective relay can only provide protection when the phase failure occurs in terminal 1, 2, 3 and among the three phases of power supply A, B and C.