Rated voltage : HV equipment10KV and 12KV, LV equipment 0.4 KV.Rated current :HV equipment 630A, LV equipment 1500A.
Designed for urban and rural power networks, it features a fully sealed and insulated structure with the HV load switch and fuse immersed in transformer oil. Its space-saving design occupies only 1/3–1/5 of the footprint of European-style substations of equivalent capacity. Suitable for high-rise buildings, residential communities, industrial parks, and temporary sites, it offers high reliability, low loss, quiet operation, and strong overload capability.
Standard: IEC1330
1. Ambient air temperature: -30℃ ~+40℃
2. Altitude: ≤1000m
3. Wind speed:34m/s ≤700pa
4. Relative humidity: Daily average relative humidity ≤95%.Monthly average relative humidity ≤95%.
5. Installation inclination: ≤grade 8
6. Applicable in the places without corrosive and flammable gas. Note: Customized products are available.
Compact & Eco-Friendly Design: Saves space and reduces environmental footprint.
Fully Sealed & Insulated: Enhances safety by eliminating exposed live parts.
Flexible Connection: Supports both loop and terminal HV configurations.
High-Efficiency Transformer: Low loss, low noise, high overload and short-circuit resistance.
Modular Connectors: Equipped with fully insulated ZnO surge arresters and 200A loadbreak elbows for hot-swapping.
1. Rated voltage: 10kV/0.4Kk
2. High voltage side rated voltage: 10kV
3. High voltage side max voltage: 12kV
4. Low voltage side rated voltage: 0.4kV
5. Rated frequency: 50Hz
6. High voltage switch thermal stability capacity: 20kA/26
7. Low voltage main circuit breaker rated short circuit breaker capacity: 35kA
8. Low voltage output circuit breaker rated short circuit breaker capacity: 35kA
9. High voltage load switch transfer current: 1500A
10. Selection of neutral earthing bus
| Rated voltage (kV) |
10 | 0.4 | ||
| Transformer | Switch to ground and interphase |
Switch isolation between fracture |
||
| Power frequency withstand voltage(kV) |
35 | 42 | 48 | 2.5 |
| The peak impact resistance(kV) |
75 | 75 | 85 | / |
11.Noise level: 50dB
12.Box shell protection grade: Not less than IP3X
YB27-12/0.4 prefabricated substation standard type Overall and mounting dimensions(mm)
| Capacity (kVA) | A | B | C | D | E | F | H | |
| Standard type | 100-250 | 1900 | 1650 | 1250 | 650/800 | 600 | 1410/1560 | 1450 |
| 315 | 1900 | 1650 | 1350 | 650/800 | 650 | 1460/1610 | 1450 | |
| 400-500 | 1900 | 1750 | 1450 | 650/800 | 650 | 1490/1640 | 1550 | |
| 630 | 1900 | 1750 | 1550 | 650/800 | 700 | 1580/1730 | 1550 | |
| 800 | 1900 | 1850 | 1550 | 650/800 | 700 | 1640/1790 | 1650 | |
| 1000 | 1900 | 1850 | 1650 | 650/800 | 700 | 1640/1790 | 1650 |
YB27-12/0.4 prefabricated substation extra-strength type Overall and mounting dimensions(mm)
| Capacity (kVA) | A | B | C | D | E | F | H | |
| Extra-Strength type | 100-250 | 2400 | 1650 | 1250 | 800 | 600 | 1560 | 1450 |
| 315 | 2400 | 1650 | 1350 | 800 | 650 | 1610 | 1450 | |
| 400-500 | 2400 | 1750 | 1450 | 800 | 650 | 1640 | 1550 | |
| 630 | 2400 | 1750 | 1550 | 800 | 700 | 1730 | 1550 | |
| 800 | 2400 | 1850 | 1550 | 800 | 700 | 1790 | 1650 | |
| 1000 | 2400 | 1850 | 1650 | 800 | 700 | 1790 | 1650 |
YB27-12/0.4 prefabricated substation comprehensiveness type Overall and mounting dimensions(mm)
| Capacity (kVA) | A | B | C | D | E | F | G | M | N | |
| Comprehensiveness type | 100-250 | 2400 | 1750 | 1250 | 800 | 600 | 1750 | 1450 | 950 | 550 |
| 315 | 2400 | 1750 | 1350 | 800 | 650 | 1750 | 1450 | 950 | 550 | |
| 400-500 | 2400 | 1850 | 1450 | 800 | 650 | 1750 | 1550 | 950 | 550 | |
| 630 | 2400 | 1850 | 1550 | 800 | 650 | 1750 | 1550 | 950 | 550 | |
| 800 | 2400 | 1950 | 1550 | 800 | 650 | 1750 | 1650 | 950 | 550 | |
| 1000 | 2400 | 1950 | 1650 | 800 | 700 | 1750 | 1650 | 950 | 550 |
Standard type and extra-strength type