Voltage and current display relay is a microprocessor-based voltage monitoring device for sinale-phase AC networks to protect electrical equipment from surge voltage. The device analyzes the main voltage and displays its curent value on a digital indicator. Load is switched by electromagnetic relay. The user can set the current voltage value and delay time through the button.The value is stored in non-volatile memory. Aluminum wires and copper wires can be used for connection.
Voltage and current display relay used in administrative, industrial and residential buildings and has the function of protecting single-phase lines:
• Undervoltage protection;
• Overvoltage protection;
• Working under voltmeter mode;
• Overcurrent proteciton.
Technical data | YC7VA | YC7V | YC7A | |||||
Rated Working Voltage | AC 220V | |||||||
Operation voltage range | AC 80V-300V | AC 80V-300V | ||||||
Rated frequency | 50Hz/60Hz | |||||||
Overvoltage(>U)setting range | 130-300V | |||||||
Undervoltage(<U)setting range | 80-210V | |||||||
Rated current | 40/63A(subject to prodect label) | 1~40/63A(subject to prodect label) | ||||||
>U and | 1-999S | Default 30S | 0.5S(>Atrip delay) | |||||
Reset/start delay | 1-999S | Default 5S | 1~999S | |||||
Voltage measurement accuracy | 2%(Not exceeding 2%of the overall range) | 1%(Not exceeding 1%of the overall range) | ||||||
Rated insulation voltage | 400V | |||||||
Output contact | 1NO | |||||||
Electrical Life | 105 | |||||||
Mechanical Life | 106 | |||||||
Protection degree | IP20 | |||||||
Pollution degree | 3 | |||||||
Altitude | ≤2000m | |||||||
Operating temperature | -50℃~55℃ | |||||||
Humidity | ≤50%at 40%(without condensation) | |||||||
Storage temperature | -30℃~70℃ | |||||||
Current specification | 15A | 25A | 32A | 50A | 63A | |||
Rated operating current(In,A) | 15 | 25 | 32 | 50 | 63 | |||
Maximum operating current Imax(A,within 10min) | 25 | 30 | 40 | 60 | 80 | |||
Max.power of load(kW) | 3.6 | 5.5 | 7 | 11 | 13.9 |
NO.Option code | Option | max | min | Default Step | Unit | Description | ||
P1 | Pt | Power-on delay | 999 | 1 | 5 | 1/10 | S | |
P2 | rt | Recoverydelay | 999 | 1 | 30 | 1/10 | S | |
P3 | oU | Overvoltage | 300 | 130 | 270 | 1/10 | V | Close overvoltage if greater than 300 |
P4 | oUr | Overvoltage recovery value | 295 | 125 | 265 | 1/10 | V | Skip this setting when overvoltage is turned off |
P5 | uU | Undervoltage | 210 | 80 | 170 | 1/10 | V | Close undervoltage if below 80 |
P6 | uUr | Undervoltage recoveryvalue | 215 | 85 | 175 | 1/10 | V | Skip this setting when undervoltage is turned off |
P7 | Utt | Overvoltage action delay | 10.0 | 0.1 | 0.5 | 0.1/1.0 | S | |
P8 | UAd | Voltage correction | +10% | -10% | 0 | 0.5% | V | Long press settingis not recommended |
P9 | oC | Overcurrent | 63.0 | 1.0 | 63.0 | 0.1/1.0 | A | Close overcurrent if greater than 63.0 |
P10 | Ctt | Overflow as delay | 10.0 | 0.1 | 1.0 | 0.1/1.0 | S | |
P11 | CC | Continuous overcurrent counting | 20 | 0 | 0 | 1 | Times | 0:Turn off counting |
P12 | CAd | Current correction | +10% | -10% | 0 | 0.5% | A | Long press settingisnot recommended |
P13 | FAd | Frequency correction | +2.5% | -2.5% | 0 | 0.1% | Hz | Modifyingthis value will affect the accuracy ofthe timer |
P14 | FPd | Rapid power failure protection | on | off | on | MS | ||
P15 | dS | Display mode | 3 | 1 | 1 | 1 | 1:Standards | |
2:Manualswitch | ||||||||
3:Automatic switch | ||||||||
P16 | Ar | Automatic reset | on | off | on | on:Self-recovery | ||
off:Manual recovery | ||||||||
P17 | Act | Action/knifemode | on | off | on | on:Protector working properly | ||
off:knife mode | ||||||||
P18 | EC | Energy saving mode | on | off | off | on:Open | ||
off:Close | ||||||||
P19 | Loc | Setuplockpassword | 999 | 000 | 112 | 1/10 | When this value is not 112,you can only view the parameter and cannot set it |