Home Categories Send inquiry

YCB9-63 MCB

General

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Release

Curve

Specifications

Type Standart EC/EN 60898-1
Electrical features Rated current In A 1,2,4,6,10,16,20,25,32,40,50,63
Poles P 1,2,3,4
Rated voltage Ue V 230/400
Insulation voltage Ui V 500
Rated frequency Hz 50/60
Rated breaking capacity A 45,006,000
Rated impulse withstand voltage(1.2/50)Uimp V 4500(80A)/6000(1-63A)
Dielectric test voltage at ind.Freq.for 1min kV 2
Pollution degree 2
Thermo-magnetic release characteristic B,C,D
Mechanical features Electrical life 8000
Mechanical life 20000
Protection degree IP20
Reference temperature for setting of thermal element 30
Ambient temperature -5~+40
(with daily average≤35℃)
Storage temperature -25~+70
Installatior Terminal connection type Cable/Pin-type busbar
Terminal size top /bottom for cable mm² 25
AWG 3月18日
Terminal size top /bottom for busbar mm 25
AWG 3月18日
Tightening torque N*m 2
In-Ibs 18
Mounting On DIN rail EN 60715(35mm)by means of fast clip
Connection From top or bottor

Overall and Mounting Dimensions(mm)