General
The YCB9-80 series miniature circuit breaker are suitable for overcurrent protection of building line facilities and similar purposes in AC 50/60Hz, rated voltage 230V/400V, rated current up to 80A circuits. They have isolation, overload, and short circuit protection functions, and can also be used for infrequent operation and switching of lines under normal circumstances.Circuit breakers are suitable for various places such as industry, commerce, high-rise buildings, and residential buildings.
Standard:IEC/EN 60898-1,IEC/EN 60947-2
YCB9 | 80 | M | 1P | C | 16 | Double busbar |
Model | Frame size rated current | Breaking capacity |
Number of poles |
Tripping characteristics |
Rated current |
Others |
Miniature circuit breaker |
80 | M:6kA H:10kA |
1P 2P 3P |
B C D |
1 |
/:Single busbar DB:Double busbar |
Note: This product c)an be assembled with accessories(YCB9-80 OF/SD/OF+SD/ MX/ MVMN/MX+OF, etc
Type | Standard | IEC/EN 60947-2 | IEC/EN 60898-1 | ||
Comprehensive data |
Function | Overload,Short circuit,Isolation | |||
Number of poles | 1P,2P,3P,4P | ||||
Rated current In | A | 1-63A | 1-80A | ||
Rated frequency | Hz | 50/60Hz | |||
Electrical features |
Rated voltage Ue | V | 230/400 | ||
Rated insulation voltage Ui | V | 500 | |||
Rated breaking capacity Icn | A | M:6000 H:10000 | |||
Rated impulse withstand voltage Uimp(1.2/50) | kA | 4 | |||
Pollution degree | 2 | ||||
Use category | II,IⅢ | ||||
Trip type | Thermal magnetic release | ||||
Thermal magnetic tripping characteristics | 8.5-12In | B,C,D | |||
Electrical and mechanical accessories | □ | ||||
Mechanical features |
Mechanical life | times | 20000 | ||
Electrical life | times | 10000 | |||
Protection degree | IP20 | ||||
Antihumidity and heat resistance | The relative humidity of the air is not more than 50%when the ambient air temperature is +40℃,and it can have a higher relative humidity at a lower temperature |
||||
Reference ambient temperature | ℃ | 30 | |||
Ambient temperature | ℃ | -5℃-+40℃,the average value of 24h does not exceed +35℃ |
|||
Height | m | Not exceeding 2000 | |||
Installation | Busbar connection type | Single or Double bus bar Anti-mistake contact terminal block | |||
Terminal connection type | Cable/U-type busbar/Pin-type busbar | ||||
Maximum wire capacity |
Terminal size top/bottom for cable | mm² | 25 | ||
AWG | 18-3 | ||||
Terminal size top/bottom for busbar | mm² | 25 | |||
AWG | 18-3 | ||||
Torque | N*m | 2 | |||
In-lbs | 18 | ||||
Tool | 18 | Phillips screwdriver or flat-blade screwdriver | |||
Installation | On DIN rail EN 60715(35mm)by means of fast clip device | ||||
Wiring method | From top or bottom |
Type | Test current | Tripping time | Expected result | Type | Test current | Tripping time | Expected result |
B,C,D | 1.13In | t≤1h(In≤63A) | Not tripping | B | 3In | t≤0.1s | Not tripping |
1.13In | t≤2h(In>63A) | C | 5In | t≤0.1s | |||
B,C,D | 1.45In | t≤1h(In≤63A) | Tripping | D | 10ln | t≤0.1s | |
1.45In | t<2h(In>63A) | B | 5In | t<0.1s | Tripping | ||
B,C,D | 2.25In | 1s<t <60s(In≤32A) | Tripping | C | 10ln | t<0.1s | |
2.25In | 1s<t<120s(In>32A) | D | 20ln | t<0.1s |
Test | Rated curent |
Test current |
Initial status | Time limit for tripping or not tripping |
Time limit for tripping or not tripping |
Remarks |
a | 1-63A | 1.05In | Cold state | t≥1h(In≤63A) t≥2h(In>63A) |
Not tripping | Current increase steadily within 5s |
b | 1.3In | Right after test number a |
t<1h(In≤63A) t<2h(In>63A) |
Tripping | ||
C | 8ln | Cold state | t≥0.2s | Not tripping | Turn on the power supply byclosing the auxiliary switch | |
d | 12In | Cold state | t<0.2s | Not tripping | Turn on the power supply byclosing the auxiliary switch |