1. Ambient temperature: -25°C ~+40°C.
2. Air conditions:At mounting site,relative humidity not exceed 50% at the maximum temperature of +40°C. For the wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature averaged in that month is +20°C , special measures should betaken to occurrence of condensation.
3. Altitude: ≤ 2000m.
4. The installation category is II and III.
5. The circuit breaker shall be installed on DIN rail EN 60715(35mm), which shall meet the A1.1 TH 35-7.5 steel mounting rail requirements.
6. Pollution grade: 2
7. Mounting conditions: inclination between mounting plane and vertical plane not exceed±5°C
8. The external magnetic field of the installation site should not exceed 5 times of the geomagnetic field in any direction.
9. The product should locate in the places where there are no obvious impact and shake.
YCB9NL-40LS Range RCBO with switched neutral built in as standard will fully isolate a faulty or damaged circuit by disconnecting live and neutral conductors . They offer the most comprehensive circuit protection available .
Using the WRB range RCBO will guarantee that healthy circuits remain in service and that only a faulty circuit is switched off. This avoids danger and prevents inconvenience in the event of a fault. They have switched neutral built in as standard , live and neutral conductors do not have to be disconnected for insulation resistance testing. This saves time and money
Type | Standard | IEC/EN 61009-1 |
Electrical features | Rated current In(A) | 2,4,6,10,16,20,25,32,40 |
Type | Electronic | |
Type(wave form of the earth leakage sensed) | A Type | |
Poles | 1P+N(Switched Live and Neutral) | |
Rated voltage Ue(V) | 230 | |
Rated sensitivity I△n | 30mA | |
Insulation voltage Ui(V) | 500 | |
Rated frequency | 50/60Hz | |
Rated breaking capacity | 6kA | |
Rated residual making and breaking capacity I△m(A) | 3000 | |
Rated impulse withstand voltage(1.2/50)Uimp(V) | 4000 | |
Break time under l△n(s) | ≤0.1 | |
Dielectric test voltage at ind.Freq.for 1 min(kV) | 2 | |
Pollution degree | 2 | |
Mechanical features | Thermo-magnetic release characteristic | B,C |
Electrical life | 2,000 | |
Mechanical life | 10,000 | |
Contact position indicator | Yes | |
Protection degree | IP20 | |
Reference temperature for setting of thermal element(℃) | 30 | |
Installation | Ambient temperature (with daily average ≤35℃) | -5~+40 |
Storage temperation(℃) | -25~+70 | |
Terminal connection type | Cable/U-type busbar/Pin-type busbar | |
Terminal size top for cable | 10mm² | |
Terminal size bottom for cable | 16mm²/18-8AWG | |
Terminal size top/bottom for Busbar | 10mm²/18-8 AWG | |
Tightening torque | 2.5 N*m /22 In-Ibs. | |
Mounting | On DIN rail EN 60715(35mm) | |
Connection | From bottom |
The maximum permissible current in a circuit breaker depends on the ambient temperature at which the circuit breaker is placed. Ambient temperature is the temperature inside the enclosure or switchboard in which the circuit breakers are installed. The reference temperature is 30°C Ambient temperature: -5°C ~+40°C.
Temperature | -10℃ | 0℃ | 10℃ | 20℃ | 30℃ | 40℃ | 50℃ | 60℃ |
Temperature compensation coefficient of rated current | 1.20 | 1.15 | 1.10 | 1.05 | 1.00 | 0.95 | 0.90 | 0.85 |
• When ordering, the customer shall indicate: the product name of RCBO, model, rated current, rated residual operating current, instantaneous tripping type, number of poles, quantity. For example: YCB9NL-40LS TYPE A 1P+N C40 100 units.
• Special requirements of customers can be negotiated separately