The YCC7 4P series contactor has four main contacts, which can control two independent load circuits or perform on-off control on three-phase four wire circuits. In the case of a three-phase four wire system, both the phase and neutral wires need to be cut off when the power is cut off.
| YC | C7 | - | 9 | 4 | 220V | 50/60Hz |
| Miniature circuit breaker |
Design Serial Number | 09:9A 12:12A 18:18A 25:25A 32:32A 40:40A 50:50A 65:65A 80:80A 95:95A |
004:Main contact 4P 4NO 008:Main contact 4P 2NO/2NC |
220V:220V 380V:380V 220V:220V 24V:24V 36V:36V 48V:48V 110V:110V 240V:240V 415V:415V |
50Hz:50Hz 60Hz:60Hz 50/60Hz:50/60Hz |
|
| Model (4P) | YCC7-09 YCC7-12 | YCC7-18 | YCC725 | YCC⁷32 | YCC738 | YOC7-40 | YCC750 | YCC765 YCC780 | YOC795 | ||||
| characteristics of main circuit | |||||||||||||
| number of poles | 4P | ||||||||||||
| Rated insulation voltage (Ui) | V | 690 | |||||||||||
| Ratedoperating voltage(Ue) | V | 380/400,660/690 | |||||||||||
| Agreed heating current (Ith), rated operating current of AC-1 |
20 | 25 | 32 | 40 | 50 | 50 | 60 | 80 | 80 | 100 | 125 | ||
| Rated work-ing current (le) |
AC- 3,380/400V |
A | 9 | 12 | 18 | 25 | 32 | 38 | 40 | 50 | 65 | 80 | 95 |
| AC- 3,660/690V |
A | 6.6 | 8.9 | 12 | 18 | 22 | 22 | 34 | 39 | 42 | 49 | 49 | |
| AC- 4,380/400V |
A | 3.5 | 5 | 7.7 | 8.5 | 12 | 14 | 18.5 | 24 | 28 | 37 | 44 | |
| AC- 4,660/690V |
A | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 8.9 | 9 | 12 | 14 | 17.3 | 21.3 | |
| Rated work-ing power (Pe) |
AC- 3,380/400V |
kW | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 18.5 | 22 | 30 | 37 | 45 |
| AC- 3,660/690V |
kW | 5.5 | 7.5 | 10 | 15 | 18.5 | 18.5 | 30 | 37 | 37 | 45 | 45 | |
| AC- 4,380/400V |
kW | 1.5 | 2.2 | 3.3 | 4 | 5.4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | |
| AC- 4,660/690V |
kW | 1.1 | 1.5 | 3 | 3.7 | 5.5 | 6 | 7.5 | 10 | 11 | 15 | 18.5 | |
| mechanical life | 10,000 times |
1200 | 1000 | 900 | 650 | ||||||||
| electric life | AC-3 | 10,000 times |
110 | 90 | 65 | ||||||||
| AC-4 | 10,000 times |
22 | 17 | 11 | |||||||||
| operation frequency |
AC-3 | Times per hour |
1200 | 600 | |||||||||
| AC-4 | Times per hour |
300 | 300 | ||||||||||
| Main circuit terminal wiring capacity | |||||||||||||
| Flexible wire | 1 wire | mm² | 1...4 | 1.5.…6 | 6...25 | 10.….50 | |||||||
| Wthteminal | 2 wires | mm² | 1...2.5 | 1.5.….4 | 4...10 | 6...25 | |||||||
| Rigid line | 1 wire | mm² | 1..4 | 1.5.…6 | 6...25 | 10.…50 | |||||||
| Without terminal blocks |
2 wires | mm² | 1...4 | 1.5.…6 | 4...10 | 6...25 | |||||||
| Tightening torque |
N ·m | 1.2 | 1.8 | 6 | 9 | ||||||||
| Coil | |||||||||||||
| Rated control circuit voltage(Us) |
50Hz | V | 24,36,48,110,127,220/230,240,380/400,415,440 | ||||||||||
| 50/60Hz | V | 24,36,48,110,127,220/230,240,380/400,415,440 | |||||||||||
| Enable control loop voltage (US) |
Operation | V | 09-38,:70%~120% | 40-95,:90%~120% | |||||||||
| Releas | V | 09-38,:20%~65% | 40-95,:20%~85% | ||||||||||
| Coil power dissipation |
Pull-in | VA | 60 | 70 | 200 | 200 | |||||||
| Holding | VA | ≤9.0 | ≤14 | ≤25 | ≤25 | ||||||||
| Model | Amax | Bmax | Cmax | Dmax | Emax | Fmax | a | b | c | d | Φ 1 | Φ 2 | |
| YCC7-09, 12, 18(4P) | 47 | 76 | 84 | 67 | 115 | 136 | 34/36 | 48.5/61.5 | - | - | 4.8 | - | |
| YCC7-25, 32, 38(4P) | 58 | 83 | 96 | 77 | 127 | 149 | 39/40 | 46/70 | - | - | 5 | - | |
| YCC7-40,50,65 (4P) | 4 | 86 | 128 | 122 | 106 | 153 | 175 | 67 | 116 | 40 | 105 | 5.5 | 6.5 |
| 8 | 124 | ||||||||||||
| YCC7-80, 95(4P) | 4 | 98 | 129 | 127 | 118 | 158 | 179 | 68 | 115 | 40.5 | 107.5 | 5.5 | 6.5 |
| 8 | 137 | ||||||||||||
The YCC7 4P Contactor is used to control motor circuits and electrical loads in industrial and commercial applications, capable of switching two independent circuits or three-phase four-wire systems.
Rated working currents range from 9A to 95A, with operating voltages from 220V to 690V AC.
It has four poles (4P), with models featuring either 4 normally open contacts or 2 normally open + 2 normally closed contacts.
YCC7 4P Contactors can be installed on DIN rails or fixed with screws.
Mechanical life is up to 10,000 operations, while electrical life varies by AC category (AC-3 up to 10,000 cycles, AC-4 up to 10,000 cycles depending on current rating).
Coil control voltages include 24V, 36V, 48V, 110V, 127V, 220/230V, 240V, 380/400V, 415V, and 440V AC/DC.
Suitable for AC-1 and AC-3 load types, including motors, pumps, compressors, and industrial machinery.
It supports flexible and rigid wires, single or double conductors, with specific cross-sections depending on current rating; tightening torque ranges from 1.2 N·m to 9 N·m.