  Product model: YCK-30/1,YCK-30/2,YCK-30/3,YCK-30/4,YCK-40/1,YCK-40/2,YCK-40/3,YCK-40/4,YCK-50/3,YCK-60/3,YCK-75/3,YCK-90/3

Operating conditions

1. Ambient temperature: -40°C~+65°C 2. Relative humidity: ≤20% at 40°C; ≤90% at 20°C 3. Altitude: ≤2000m 4. Environmental conditions: no harmful gases and vapors, no conductive or explosive dust, no severe mechanical vibration

Technical parameter

Dielectric Strength Between contactandcoil:2200VAC
Between poles:2200VAC
Between open contacts:2200VAC
Ar extinguishing cover Standard configuration
Insulation materials 130°℃ Class B
Temperature range -40℃ to+65℃,-40F to+150F
Weight 50-60FLA0.91kg,75-90FLA1.81kg
Terminal type Aluminum pressure wire box
Wiring size 50/60FLA crimping box 14-2
75/90FLAcrimping box 14-1
Recommended
locking torque
Crimping box 5.67N.m
Coil terminal Quick connect terminal Double.250 "insert or#6-32 screw/.250"insert
Main circuit terminal Double.250 "Insert

 

Coil Voltage YCK-30/1,YCK-40/1 One pole contactor YCK-30/2,YCK-40/2 Two pole contactor
24  120  208/240 277  24  120  208/240 277 
Coil resistance 18  420  1800  2500  11  237  1000  1600 
Pull-in voltage 18  88  177  221  18  88  177  221 
Release voltage 6-15 20-70 40-140 50-165 6-15 20-70 40-140 50-165
Power consumption ofsuction ·50Hz 31  31  31  31  33  33  33  33 
Power consumption of suction ·60Hz 28  28  28  28  30  30  30  30 
Maintain power consumption-50Hz
Maintain power consumption-60Hz 6.5  6.5  6.5  6.5 
Maximum coil voltage 30  132  264  300  30  132  264  300 
 
Coil Voltage YCK-30/3,YCK-40/3 Triple pole contactor YCK-30/4,YCK-40/4 Quadru pole contactor
24  120  208/240 277  24  120  208/240 277 
Coil resstance 180  720  900  150  600  750 
Pull-in voltage 18  88  177  221  18  88  177  220 
Release voltage 6-15 20-70 40-140 50-165 6-15 20-70 40-140 65-185
Power consumption ofsuction ·50Hz 65  65  65  65  62  62  62  62 
Power consumption of suction ·60Hz 60  60  60  60  59  59  59  59 
Maintain power consumption-50Hz 7.5  7.5  7.5  7.5 
Maintain power consumption-60Hz
Maximum coil voltage 30  132  264  300  30  132  264  300 

 

Coil Voltage YCK-50/3,YCK-60/3 contactor YCK-75/3,YCK-90/3 contactor
24  120  208/240 277  24  120  208/240 277 
Coil resistance 180  720  900  0.65  16  64  85 
Pull-in voltage 18  93  177  235  18  88  177  220 
Release voltage 6-15 20-70 40-140 50-165 6-15 20-70 40-110 65-185
Power consumption ofsuction ·50Hz 140  140  140  140  285  285  285  285 
Power consumption of suction ·60Hz 132  132  132  132  240  240  240  240 
Maintain power consumption-50Hz 20  20  20  20  42  42  42  42 
Maintain power consumption-60Hz 14  14  14  14  27  27  27  27 
Maximum coil voltage 30  132  264  300  30  132  264  300 