YCL7 AC85V-265V
| Model | New | Serial number | Voltage |
| YC | L | 7 | AC85V-265V |
| Model | Residual current | Serial number | AC85V-265V |
1.Ambient temperature:-5℃~+40℃
2. Relative humidity:≤20% at 40℃;≤90% at 20℃
3. Altitude:≤2000m
4. Environmental conditions: no harmful gases and vapors, no conductive or explosive dust,no severe mechanical vibration
| Model | YCL7 |
| Function | Earth leakage Relay |
| Voltage range | AC85-265V 50/60Hz |
| Burden | 3VA |
| Operation range | 30,100,300,500mA and 1,3,5,10,20,30A |
| Trip level limits | 95%to 105%of setvalue |
| Trip time delay | 0,0.15,0.25,0.5,1,2,3,5,7.5,9sec NA when leakage level set 30mA |
| Reset time | ~1sec |
| Response time | ≤30ms(if trip current≥5×setvalue) |
| ≤50ms(if trip current=1×setvalue) | |
| Hysteresis | 15% |
| ZCT detection | absent or short |
| Accuracy | Trip:±5%of set trip current Time:±5%of set time±50ms |
| Reset mode | Manual/Auto reset |
| Output | 1×SPDT |
| Current rating | 10AAC1 |
| Switching voltage | 250VAC/24VDC |
| Min.breaking capacity DC | 500mW |
| Mechanical life | 1X10⁷ |
| Electrical life(AC1) | 1X10⁵ |
| Protection degree | IP20 |
| Examine | A type true RMS measurement ZCT detection |
| Rank | User selectable trip time delay,leakage current levels |
Note:
1. Disconnect Y1-C, operate in manual reset mode, short circuit Y1 and C, operate in auto reset mode.
2. The cable connecting ZCT and the product should use shielded cable or twisted pair cable(21m).
3. The cable for remote control of "test" and "reset" should be≤10m.