Home Categories Send inquiry

YCM1LE Earth Leakage MCCB

Note

Without current release components, N-Pole is alwaus at making status, not makes and breaks with other three poles;
Without current release components, N-Pole makes with the other three poles(NPole first makes then breaks);

Technical data
Type YCM1LE-125 YCM1LE-250 YCM1LE-400 YCM1LE-630
YCM1LE-800
Frame current  Inm(A) 125 250 400 630
800
Rated current  In(A) 10, 16, 20, 25, 32, 40,50, 63, 80, 100, 125 100, 125, 140, 160,180, 200, 225, 250 225, 315, 350, 400 400, 500, 630
630, 700, 800
Pole 2 3 4 2 3 4 3 4 3 4
Rated insulation voltage AC800
Ui(V)
Rated working voltage AC400
Ue(V)
Rated impulse withstand 8000
voltage  Uimp(V)
Arcing-over distance 50 100
(mm)
Breaking ability level L M L M L M L M
Rated ultimate short-circuit 35 50 35 50 50 65 50 65
breaking capacity  Icu(kA)
Rated working short-circuit 22 25 22 25 35 42 35 42
breaking capacity  Ics(kA)
Rated residual short-circuit 7.5 12.5 7.5 12.5 12.5 13.5 12.5 13.5
breaking capacity
Rated residual operating current  IΔn(mA) No time-delay type 30/100/500/100/300/500 30/100/500/100/300/500 100/300/500 300/500/1000
  Time-delay type 100/300/500 100/300/500 100/300/500 300/500/1000
Rated residual unoperating current  IΔn(mA)   1/2 IΔn 1/2 IΔn 1/2 IΔn 1/2 IΔn
Operating performance (times) Power on 1500 1000 1000 1000
Power off 8500 7000 4000 4000
Total times 10000 8000 5000 5000
Residual current protection opreating time   IΔn 2IΔn 5IΔn 10IΔn
Max. breaking time(s) No time-delay type 0.2 0.1 0.04 0.04
Time-delay 0.4/1 0.4/1 0.3/1 0.3/1
type

 

Type Pole Overall size (mm) Installation size (mm)
A B C D a b Φd
YCM1LE-125 3 92 150 110 92 30 129 4.5
4 122 60
YCM1LE-250 3 107 165 110 90 35 126 4.5
4 142 70
YCM1LE-400 3 150 257 146.5 106.5 44 194 7
4 198 94
YCM1LE-630 YCM1LE-800 3 210 280 155 115.5 70 243 7
4 280 140