Notes:
Classified into Type L(standard type)and Type M(high breaking type)according to the level of rated ultimate short-circuit breaking capacity.
No code for direct handle operation;code “P”for electric operation;code “Z”for rotating handle operation.
No code for power distribution circuit breakers;code“2”for motor protection circuit breakers.The products are divided into 3-pole and 4-pole types.Among 4-poe products,the neutralpole(N-pole)has 2 types:
Type A:No overcurrent tripper is installed on the N-pole,and the N-pole is always on and does not switch on or off together with the other three poles.
Type B:No overcurrent tripper is installed on the N-pole,and the N-pole switches on and off together with the other three poles (the N-pole switches on first and off last).
1.Ambient temperature:-5℃~+40℃
2.Altitude:2000m
3.Humidity:The relative humidity of air shall not exceed 50%at+40°℃.
4.Pollution degree:Grade 3
5.Installation category:Category Ⅲ
6.Places free from rain and snow erosion.
7.Places free from metals,gases that damage insulation,and conductive dust.
8.Places free from explosive media and media that are corrosive enough to damage the product.
9.Installation method:Vertical installation,horizontal installation.
10.Transportation and Storage Conditions:Between-25℃ and+55℃ under normal conditions.
11.Short-term temperature:It can reach up to+70℃ for a short period (24 hours).
Tripper Operation Performance
For Power Distribution
| Rated Operating Current of Tripper(In) |
Thermal Tripper(Reference Temperature 40℃) | Electromagnetic Tripper Operating Current (A) |
Remarks | |
| 1.05In [Cold State]Non- operation Time |
1.30In(Hot State) Operation Time |
|||
10| ≥1 |
<1 |
10ln ±20% |
Power distribution protector.Note: |
For 1000A,it's 7In±20% |
63| ≥2 |
<2 |
10ln ±20% |
| |
100| ≥2 |
<2 |
5In ±20% |
7In ±20% 10In±20% | |
|
Note:Circuit breakers with a rated current less than 160A do not have tripping at 5In current.
|
||||
For Motor Protection
| Rated Operating Current of Tripper(In)(A) |
Thermal Tripper(Reference Temperature 40℃) | Electromagnetic Tripper Operating Current (A) |
|||
| 1.0ln [Cold State]Non- operation Time(h) |
1.20In (Hot State) Operation Time(h) |
1.50In (Hot State) Operation Time(h) |
7.2ln [Cold State]Non- operation Time(h) |
||
10| ≥2 |
≤2 |
8min |
6s | 12In±20% |
|
Circuit Breaker Power Loss
| Model | Energized current |
Three-pole Total Power Loss(W) | ||
| Front-panel wiring, rear-panel wiring |
Plug-in front-panel wiring |
Plug-in rear-panel wiring |
||
| YCM6i-63/125 (L,M)Direct heating type(10A-25A) | 25 | 28 | 1 | 32 |
| YCM6i-63/125(L,M)Indirect heating type(32A-63A) | 63 | 20 | / | 24 |
| YCM6i-160(L,M)Indirect heating type(32A-100A) | 125 | 35 | 37 | 40 |
| YCM6i-250(L,M) | 250 | 62 | 66 | 70 |
| YCM6i-400/630(L,M) | 400 | 115 | 120 | 125 |
| YCM6i-800(L,M) | 630 | 187 | 193 | 200 |
| YCM6i-1000(M) | 800 | 262 | / | 300 |
Derating Factor of Circuit Breaker with Ambient Temperature Change
| Model | Derating Factor(In) | ||||
| +40℃ | +45℃ | +50℃ | +55℃ | +60℃ | |
| YCM6i-63/125 | 1 | 0.94 | 0.88 | 0.81 | 0.74 |
| YCM6i-160 | 1 | 0.96 | 0.91 | 0.85 | 0.78 |
| YCM6i-250 | 1 | 0.97 | 0.94 | 0.90 | 0.86 |
| YCM6i-400/630 | 1 | 0.95 | 0.89 | 0.82 | 0.75 |
| YCM6i-800 | 1 | 0.94 | 0.88 | 0.82 | 0.76 |
| YCM6i-1000 | 1 | 0.94 | 0.87 | 0.80 | 0.72 |
| Notes:The above derating factors are measured under the frame-level rated current. | |||||
| Frame rating current Inm(A) | 63/125 | 160 | 250 | 400 | 630 | 800 | 1000 | |||||||||
| Rated current In(A),40℃ | 10,16,20,25, 32,40,50,63, 80,100,125 |
25,32,40,50, 63,80,100, 125,160 |
125,160,180, 200,225,250, |
250,315,350,400 | 400,500,630 | 630,700,800 | 800, 1000 |
|||||||||
| insulation voltage Ui(V) | 800 | 1000 | 1000 | 1000 | 1000 | 1140 | 1140 | |||||||||
| Rated impulse withstand voltage Uimp(KV) | 8 | 12 | 12 | 12 | 12 | 12 | 12 | |||||||||
| Rated operating voltage Ue (V) | 400,690 | 400,690 | 400,690 | 400,690 | 400,690 | 400,690 | 400,690 | |||||||||
| Selectivity category | A | A | A | A | A | A | A | |||||||||
| Arcing distance(mm) | <50 | <50 | <50 | <50 | <100 | <100 | <120 | |||||||||
| Operating performance (times) |
Electrical life (with current supply) |
1500 | 1000 | 1000 | 1000 | 1000 | 500 | 500 | ||||||||
| Mechanical life (without current supply) |
8500 | 7000 | 7000 | 4000 | 4000 | 2500 | 2500 | |||||||||
| Breaking capacity class | L | M | L | M | L | M | L | M | L | M | L | M | L | M | ||
| Number of poles | 3P | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | |
| 4P | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ■ | ||
| Rated ultimate short-circuit breaking capacity Icu(kV) |
Ue=AC400V | 35 | 50 | 35 | 85 | 35 | 85 | 50 | 100 | 50 | 100 | 75 | 100 | 75 | 100 | |
| Rated service short-circuit breaking capacity Ics(kV) |
20 | 35 | 22 | 50 | 22 | 50 | 35 | 75 | 35 | 75 | 50 | 65 | 50 | 65 | ||
| Overall dimensions Width (W)×Height(H)×Depth (D) |
W | 3P | 75 | 92 | 72 | 107 | 150 | 150 | 182 | 210 | ||||||
| 4P | 100 | 122 | 122 | 142 | 198 | 198 | 240 | 280 | ||||||||
| H | 130 | 130 | 130 | 165 | 257 | 257 | 270 | 280 | ||||||||
| D | 67 | 77.5 | 78 | 110 | 110 | 118 | 120 | |||||||||
| Notes:The symbol““indicates not applicable,The symbol““indicates applicable. | ||||||||||||||||
| Notes:For models 63-125,the minimum instantaneous operating curent is 40A,and those below 40A are equivalent to 40A.For the 160 frame size,the instantaneous operating current below 50A is equivalent to 50A. |
||||||||||||||||
| Note:For the 2P version of models 125-250,refer to the detailed dimension page for overall and installation dimensions. | ||||||||||||||||
Description: The characteristic curve is measured under cold conditions and three-phase load.