General
YCM8-HU series AC molded case circuit breaker is suitable for AC grid circuits with rated voltage up to AC1140V and rated current of 800A.
The circuit breaker has the functions of overload long-time delay protection and short-circuit instantaneous protection, and is used to distribute electric energy and protect lines and power supply equipment from overload, short circuit and other faults.
Features
Ultra-wide breaking capacity:
rated working voltage up to AC1140V and rated current up to 800A. Under AC800V working conditions, Icu=Ics=36.5KA, ensuring reliable short-circuit protection.
Ultra-long arc-extinguishing chamber: the arc-extinguishing chamber has been improved as a whole, with more arc extinguishing plates, greatly improving the product's breaking characteristics.
Application of narrow-slot arc-extinguishing technology:advanced current-limiting and narrow-slot arc-extinguishing technology is applied,which enables the high voltage and high short-circuit current to be cut off very quickly, facilitating the extinguishing of the arc in the shortest possible time, effectively limiting the energy and current peak, and greatly reducing damage to cables and equipment caused by short-circuit currents.
Selection | ||||||||||
YCM8 | 250 | S | HU | / | 3 | 125A | AC800 | |||
Model | Shell frame current |
Breaking capacity |
Product type |
/ | Number of poles |
Rated current |
Rated voltage |
|||
YCM8 | 250(63~250) 320(250~320) 400(225~400) 630(500~630) 800(700~800) |
S:Standard breaking N:Higher breaking |
HU: AC high voltage |
/ | 3 | 63,80,100,125 140,160,180 200,225,250 280,315,320 350,400,500 630,700,800 |
AC800 AC1140 |
|||
Accessory selection rules | ||||||||||
YCM8 | MX | 1 | AC230V | |||||||
Model | Accessories | Adapter shell frame |
Accessory voltage |
|||||||
YCM8 | OF:Auxiliary contact MX:Shunt release SD:Alarm module Z:Manual operation mechanism P:Electric operating mechanism TS2:Terminal shield 2P TS3:Terminal shield 3P |
1:250/320 2:400/630/800 |
MX: AC110V AC230V AC400V DC24V |
P: AC400V AC230V DC220V |
Technical data
Model |
YCM8- 250HU |
YCM8- 320HU |
YCM8- 400HU |
|||||||||||||||||||||||
Appearance |
|
|
|
|||||||||||||||||||||||
Shell frame current Inm(A) |
250 |
320 |
400 |
|||||||||||||||||||||||
Number of poles of products |
|
|
3 |
|||||||||||||||||||||||
AC working voltage(V) |
415 |
690 |
800 |
1140 |
415 |
690 |
800 |
1140 |
415 |
690 |
800 |
1140 |
||||||||||||||
Rated insulation voltageUi(V) |
AC1150 |
AC1150 |
AC1150 |
|||||||||||||||||||||||
Rated impulse withstand voltage Uimp(KV) |
8 |
8 |
12 |
|||||||||||||||||||||||
Rated current In(A) |
63, 80, 100, 125, 140, 160, 180, 200, 225, 250 |
280, 315, 320 |
225, 250, 315, 350, 400 |
|||||||||||||||||||||||
Ultimate short-circuit breaking capacity Icu (kA) |
S |
85 |
50 |
36.5 |
10 |
85 |
50 |
36.5 |
10 |
85 |
50 |
36.5 |
10 |
|||||||||||||
N |
/ |
/ |
100 |
60 |
50 |
15 |
||||||||||||||||||||
Running short-circuit breaking capacity Ics(kA) |
Ics=100%Icu |
|||||||||||||||||||||||||
Wiring method |
Up in and down out, down in and up out, Down in and up out, up in and down out(3P) |
|||||||||||||||||||||||||
Isolation function |
Yes |
|||||||||||||||||||||||||
Tripping type |
Thermal-magnetic type |
|||||||||||||||||||||||||
Electrical life(time) |
3000 |
3000 |
2000 |
3000 |
3000 |
2000 |
1000 |
1000 |
700 |
|||||||||||||||||
Mechanical life(time) |
20000 |
20000 |
10000 |
|||||||||||||||||||||||
Standard |
IEC/EN60947-2 |
|||||||||||||||||||||||||
Attached accessories |
Shunt、Alarm、Auxiliary、Manual operation、Electric operation |
|||||||||||||||||||||||||
Certifications |
CE |
|||||||||||||||||||||||||
Overall dimension (mm) |
|
|
Width(W) |
107 |
107 |
182 |
||||||||||||||||||||
Height(H) |
180 |
180 |
250 |
|||||||||||||||||||||||
Depth(D) |
126 |
126 |
165 |
Note: ① 2P connection in series, ② 3P connection in series
Technical data
Model |
YCM8-630HU |
YCM8-800HU |
|||||||||||||||||
Appearance |
|
|
|||||||||||||||||
Shell frame current Inm(A) |
630 |
800 |
|||||||||||||||||
Number of poles of products |
3 |
3 |
|||||||||||||||||
AC working voltage(V) |
415 |
690 |
800 |
1140 |
415 |
690 |
800 |
1140 |
|||||||||||
Rated insulation voltageUi(V) |
AC1150 |
AC1150 |
|||||||||||||||||
Rated impulse withstand voltage Uimp(KV) |
12 |
12 |
|||||||||||||||||
Rated current In(A) |
500, 630 |
630,700, 800 |
|||||||||||||||||
Ultimate short-circuit breaking capacity Icu (kA) |
S |
85 |
50 |
36.5 |
10 |
85 |
50 |
36.5 |
10 |
||||||||||
N |
100 |
60 |
50 |
15 |
100 |
60 |
50 |
15 |
|||||||||||
Running short-circuit breaking capacity Ics(kA) |
Ics=100%Icu |
||||||||||||||||||
Wiring method |
Up in and down out, down in and up out, Down in and up out, up in and down out(3P) |
||||||||||||||||||
Isolation function |
Yes |
||||||||||||||||||
Tripping type |
Thermal-magnetic type |
||||||||||||||||||
Electrical life(time) |
1000 |
1000 |
1000 |
700 |
1000 |
1000 |
1000 |
700 |
|||||||||||
Mechanical life(time) |
5000 |
5000 |
|||||||||||||||||
Standard |
IEC/EN60947-2 |
||||||||||||||||||
Attached accessories |
Shunt、Alarm、Auxiliary、Manual operation、Electric operation |
||||||||||||||||||
Certifications |
CE |
||||||||||||||||||
Overall dimension (mm) |
|
|
Width(W) |
182 |
182 |
||||||||||||||
Height(H) |
250 |
250 |
|||||||||||||||||
Depth(D) |
165 |
165 |
Accessories
Accessory code |
Accessory name |
250/320HU |
400/630/800HU |
|
SD |
Alarm contact |
|
|
|
|
|
|
|
|
MX |
Shunt release |
|
|
|
|
|
|
|
|
OF |
Auxiliary contact(1NO1NC) |
|
|
|
OF+OF |
Auxiliary contact(2NO2NC) |
|
|
|
|
|
|
|
|
MX+OF |
Shunt release+ Auxiliary contact(1NO1NC) |
|
|
|
|
|
|
|
|
OF+OF |
2 sets of auxiliary contacts(2NO2NC) |
|
|
|
MX+SD |
Shunt release + Alarm contact |
|
|
|
|
|
|
|
|
OF+SD |
Auxiliary contact + Alarm contact |
|
|
|
|
|
|
|
|
MX+OF+SD |
Shunt release Auxiliary contact(1NO1NC)+ Alarm contact |
|
||
OF+OF+SD |
2 sets of auxiliary contacts(2NO2NC)+Alarm contact |
|
|
Auxiliary contact
Auxiliary contact current parameters
Rated current of shell frame grade |
Agreed heating current Ith |
The rated working current at AC 400V |
Inm<320 |
3A |
0.30A |
Inm>400 |
6A |
0.40A |
Auxiliary contact and its combination
When the circuit breaker is in the "off" position |
F12 F14 F22 F24 |
|
F11 F21 |
F12 F14 |
|
F11 |
|
When the circuit breaker is in the "on" position |
F12 F14 |
F11 |
|
F22 F24 |
F21 |
||
F12 F14 |
|
F11 |
Alarm contact
Alarm contact and its combination
Alarm contact Ue=220V, Ith=3A |
|
||
When the circuit breaker is in the "off"and "on"position |
B14 B14 |
|
B11 |
When the circuit breaker is in the "free trip" position |
B14 B12 |
|
B11 |
Shunt release
Generally installed in the Phase A of the circuit breaker, when the rated control power voltage is between 70% - 110%, the shunt releaseshall make the circuit breaker trip reliably under all operating conditions.
Control voltage: conventional: AC 50Hz, 110V, 230V, 400V, DC 24V.
Note: when the power supply of the control circuit is DC24V, the following figure is recommended for the design of the shunt control circuit.
KA: DC24V intermediate relay, contact current capacity is 1A
K: the microswitch in series with the coil inside the release aid is a normally closed contact. When the circuit breaker is disconnected, the contact will automatically disconnect and close when it is closed.
Wiring diagram
Installation method and overall dimension of external accessories
Model and specification of rotating operating handle mechanism
Model |
Installation dimension(mm) |
Central value of the operating handle relative to the circuit breaker(mm) |
|||
A |
B |
H |
D |
||
YCM8-250/320HU |
157 |
35 |
55 |
50-150 |
0 |
YCM8-400/630/800HU |
224 |
48 |
78 |
50-150 |
±5 |
Schematic diagram of hole opening of rotating operating handle
Overall and mounting dimension of external accessories
Model and specification of rotating operating handle mechanism
Model |
H |
B |
B1 |
A |
A1 |
D |
YCM8-250/320HU |
188.5 |
116 |
126 |
90 |
35 |
4.2 |
YCM8-400/630/800HU |
244 |
176 |
194 |
130 |
48 |
6.5 |
Model |
L |
A |
B |
C |
E |
||
Without zero arcing cover |
With zero arcing cover |
Without zero arcing cover |
With zero arcing cover |
||||
YCM8-250HU |
40 |
100 |
165 |
40 |
40 |
100 |
165 |
YCM8-320HU |
40 |
100 |
165 |
40 |
40 |
100 |
165 |
YCM8-400HU |
40 |
100 |
165 |
40 |
40 |
100 |
165 |
YCM8-630HU |
40 |
100 |
165 |
40 |
40 |
100 |
165 |
YCM8-800HU |
40 |
100 |
165 |
40 |
40 |
100 |
165 |