Home Categories Send inquiry

YCM8N Series MCCB

 

Operating conditions

1. Altitude: Below 2000m

2. Temperature: The temperature of media is not higher than 40°C ( +45°C for marine products) and not lower than -5°C.

3. Can withstand the bad environment of damp air, mold, radiation.

4. The maximum inclination is 22.5 degree.

5. Can work reliably under normal vibration of ship.

6. Can work reliably under earthquake(4g).

7. Should be no rain and snow hit.

8. The media should be no explosion danger and no gas which can corrode the metal or destroy the insulating or conductive dust.

Type designation

Type Frame Inm Breaking capacity Icu/lcs(kA) Operation Poles
YCM8N 125  S P
MCCB 125,250,400,630 125  15/10
250 25/18
400 35/25
630 35/25
  Default—handle direct operation;
  P—electric operation
  Z—rotating handle operation
3:three poles

 

Tripping mode and inner accessory Application Rated current(A)
300  125A
The first number indicate release mode
2: only with the instantaneous release device
3: complex release
Note: the last two numbers are attachment code
(see attachment table)
1: for distribution
2: for protecting the motor
125  10,16,20,32,40,50,63,80,100,125
250  100,125,140,160,180,200,225,250
400  250,300,315,350,400
630  400,500,630

Product Accessories

Accessory Product List

• Electrical Accessories: Shunt Trip, Undervoltage Release, Auxiliary Contact, Alarm Cotact,Integrated Auxiliary & Alarm Contact

• Mechanical Accessories: Phase Spacer, Extension Terminal, Manual Operating Mechnism, Electrical Operating Mechanism

• Installation Accessories: Fixed Plate Rear Accessory, Plug-in Accessory

Overview

Inner accessories

Accessories of YCM8, YCM8LE, YCM8T/A, YCM8RT, YCM8E are the same.

Technical data

Technical Parameters

The thermal trip unit of the circuit breaker features an inverse time-delay characteristic;The magnetic trip characteristics are shown in Table 2 (for distribution use)

Table 2 Tripping Characteristics of Thermal-Magnetic and Magnetic

Trip Units

Rated Tripping
Current(A)
Thermal-magnetic trip unit(ambient temperature +40°℃) Operating current of the
magnetic trip unit(A)
1.05In(cold state)
Non-operating time (h)
1.30ln(hot state)
operating time (h)
10≤In≤63 6ln±20%,8ln±20%10ln
±20%,7In±20%
63
Note:The non-operating time of the motor protection cirrcuit breaker is 2h at 1.0ln;the operating current is 1.20ln(hot state),and the operating
time is 2h.The operating current of the electromagnetic release is 12In±20%.

 

Curve

Altitude Derating

When the altitude is below 2000m, it will not affect the performance of the circuit breaker. When exceeding this altitude, the decrease in air insulation characteristics and cooling capacity must be considered; the following correction factors are used for installations at altitudes exceeding 2000m:

Altitude(m) 2000  2500  3000  3500  4000  4500  5000 
Insulation Voltage Ui(V) 800  728  728  664  664  616  616 
Impulse Withstand Voltage Uimp(kV) 6.5  6.5 
Maximum Working Voltage Ue(V) 690  690  690  660  660  600  550 
Thermal Rating In(A)at 40℃Ambient Temperature 1.0ln 0.98ln 0.94In 0.92In 0.88ln 0.86ln 0.85In
Note:In high-altitude environments,the breaking capacity needs to be derated according to the corresponding rated working voltage,generally
selected between 75%and 50%,which is inversely proportional to the altiude.For details,please communicate with the technical department

Temperature Influence Characteristics

Influence of High Temperature on Release Performance (High Temperature Derating Characteristics)

When the temperature exceeds 40°C, the overload protection will have slight changes. In the release time/current curve, the Ir setting value of the circuit breaker must be corrected according to the following coefficients I/Ir.

Model Ambient Temperature(℃)
40  45  50  55  60 
YCM8N-125 0.96  0.89  0.83  0.75 
YCM8N-250 0.92  0.85  0.79  0.71 
YCM8N-400/630 0.94  0.87  0.81  0.73 

 Mechanical Accessories



Phase Spacers
·Phase spacers can enhance the  insulation  performance  between  phase conductors and
    can be installed from the front slot even after the switch is installed.
·Phase spacers are standard equipment,with 4  pieces for a 3P circuit  breaker.
Extension Terminals
Extension terminals are connected to the standard terminals of the circuit breaker to pro vide various wiring solutions in a small space:
• Straight extension terminals
• Pole pitch extension terminals
Busbars and extension terminals can be connected to the inlet or outlet end of the circuit
breaker.
Handle Operating Mechanism
·The  circuit  breaker  is  operated  by  rotating  the  handle.The  ergonomically  designed  ro-
   tating handle makes the operation of the circuit breaker more flexible.
·There  are two forms  of  rotating  handle  operating  mechanisms:
Direct rotating handle (round hand operation,square hand operation)
Extended rotating handle (round extended hand operation,square extended hand oper-
ation)
·User   visual    information/settings:
Three   position   indications:OFF,ON,TRIP
The circuit breaker cannot be closed when the door is open.
The door cannot be opened when closed.
The shaft length of the extended handle can be customized according to the distance
from the back of the circuit breaker to the door.
·Hand  operation  installation  diagram,accessory  installation  diagram


Hand operation external dimensions

 
 

CD2 Electric Operator

Electrical Characteristics and Wiring Diagram
 

Electrical Accessories

 

 

Overall and mounting dimensions(mm)

Type Overall size(mm)
W L H A B W1 L1 L2 H1 H2 D D1
YCM8N-125 75  130  84  112  25  26  117  75  56  66  φ4 M6
YCM8N-250 106  165  101  126  35  35  147  97  69  78  φ5 M8
YCM8N-400/630 150  157  150  194  44  48  224  156  102  112  φ14 M10