1. Altitude: Below 2000m
2. Temperature: The temperature of media is not higher than 40°C ( +45°C for marine products) and not lower than -5°C.
3. Can withstand the bad environment of damp air, mold, radiation.
4. The maximum inclination is 22.5 degree.
5. Can work reliably under normal vibration of ship.
6. Can work reliably under earthquake(4g).
7. Should be no rain and snow hit.
8. The media should be no explosion danger and no gas which can corrode the metal or destroy the insulating or conductive dust.
Type | Frame Inm | Breaking capacity Icu/lcs(kA) | Operation | Poles |
YCM8N | 125 | S | P | 3 |
MCCB | 125,250,400,630 | 125 15/10 250 25/18 400 35/25 630 35/25 |
Default—handle direct operation; P—electric operation Z—rotating handle operation |
3:three poles |
Tripping mode and inner accessory | Application | Rated current(A) | |||
300 | 2 | 125A | |||
The first number indicate release mode 2: only with the instantaneous release device 3: complex release Note: the last two numbers are attachment code (see attachment table) |
1: for distribution 2: for protecting the motor |
125 10,16,20,32,40,50,63,80,100,125 250 100,125,140,160,180,200,225,250 400 250,300,315,350,400 630 400,500,630 |
Accessory Product List
• Electrical Accessories: Shunt Trip, Undervoltage Release, Auxiliary Contact, Alarm Cotact,Integrated Auxiliary & Alarm Contact
• Mechanical Accessories: Phase Spacer, Extension Terminal, Manual Operating Mechnism, Electrical Operating Mechanism
• Installation Accessories: Fixed Plate Rear Accessory, Plug-in Accessory
Accessories of YCM8, YCM8LE, YCM8T/A, YCM8RT, YCM8E are the same.
The thermal trip unit of the circuit breaker features an inverse time-delay characteristic;The magnetic trip characteristics are shown in Table 2 (for distribution use)
Table 2 Tripping Characteristics of Thermal-Magnetic and Magnetic
Trip Units
Rated Tripping Current(A) |
Thermal-magnetic trip unit(ambient temperature +40°℃) | Operating current of the magnetic trip unit(A) |
|
1.05In(cold state) Non-operating time (h) |
1.30ln(hot state) operating time (h) |
||
10≤In≤63 | 1 | 1 | 6ln±20%,8ln±20%10ln ±20%,7In±20% |
632 |
2 |
| |
Note:The non-operating time of the motor protection cirrcuit breaker is 2h at 1.0ln;the operating current is 1.20ln(hot state),and the operating time is 2h.The operating current of the electromagnetic release is 12In±20%. |
When the altitude is below 2000m, it will not affect the performance of the circuit breaker. When exceeding this altitude, the decrease in air insulation characteristics and cooling capacity must be considered; the following correction factors are used for installations at altitudes exceeding 2000m:
Altitude(m) | 2000 | 2500 | 3000 | 3500 | 4000 | 4500 | 5000 |
Insulation Voltage Ui(V) | 800 | 728 | 728 | 664 | 664 | 616 | 616 |
Impulse Withstand Voltage Uimp(kV) | 8 | 7 | 7 | 6.5 | 6.5 | 6 | 6 |
Maximum Working Voltage Ue(V) | 690 | 690 | 690 | 660 | 660 | 600 | 550 |
Thermal Rating In(A)at 40℃Ambient Temperature | 1.0ln | 0.98ln | 0.94In | 0.92In | 0.88ln | 0.86ln | 0.85In |
Note:In high-altitude environments,the breaking capacity needs to be derated according to the corresponding rated working voltage,generally selected between 75%and 50%,which is inversely proportional to the altiude.For details,please communicate with the technical department |
Influence of High Temperature on Release Performance (High Temperature Derating Characteristics)
When the temperature exceeds 40°C, the overload protection will have slight changes. In the release time/current curve, the Ir setting value of the circuit breaker must be corrected according to the following coefficients I/Ir.
Model | Ambient Temperature(℃) | ||||
40 | 45 | 50 | 55 | 60 | |
YCM8N-125 | 1 | 0.96 | 0.89 | 0.83 | 0.75 |
YCM8N-250 | 1 | 0.92 | 0.85 | 0.79 | 0.71 |
YCM8N-400/630 | 1 | 0.94 | 0.87 | 0.81 | 0.73 |
Phase Spacers |
·Phase spacers can enhance the insulation performance between phase conductors and can be installed from the front slot even after the switch is installed. |
·Phase spacers are standard equipment,with 4 pieces for a 3P circuit breaker. |
Extension Terminals |
Extension terminals are connected to the standard terminals of the circuit breaker to pro vide various wiring solutions in a small space: |
• Straight extension terminals • Pole pitch extension terminals |
Busbars and extension terminals can be connected to the inlet or outlet end of the circuit breaker. |
Handle Operating Mechanism |
·The circuit breaker is operated by rotating the handle.The ergonomically designed ro- tating handle makes the operation of the circuit breaker more flexible. ·There are two forms of rotating handle operating mechanisms: |
Direct rotating handle (round hand operation,square hand operation) |
Extended rotating handle (round extended hand operation,square extended hand oper- ation) |
·User visual information/settings: |
Three position indications:OFF,ON,TRIP |
The circuit breaker cannot be closed when the door is open. The door cannot be opened when closed. |
The shaft length of the extended handle can be customized according to the distance from the back of the circuit breaker to the door. |
·Hand operation installation diagram,accessory installation diagram |
Hand operation external dimensions
Electrical Characteristics and Wiring Diagram
Type | Overall size(mm) | |||||||||||
W | L | H | A | B | W1 | L1 | L2 | H1 | H2 | D | D1 | |
YCM8N-125 | 75 | 130 | 84 | 112 | 25 | 26 | 117 | 75 | 56 | 66 | φ4 | M6 |
YCM8N-250 | 106 | 165 | 101 | 126 | 35 | 35 | 147 | 97 | 69 | 78 | φ5 | M8 |
YCM8N-400/630 | 150 | 157 | 150 | 194 | 44 | 48 | 224 | 156 | 102 | 112 | φ14 | M10 |