1. Installation altitude≤2000m
2. Ambient air temperature -5℃ ~+40℃ average temperature of 24 hours must below +35℃
3. Relative humidity below 90% when the temperature is +25℃±5℃
4. Ambient pollution level: 3
5. Installation category of the starter: III
Acting characteristic of each phase in distribution circuit breaker in the load balanced condition
No. | Multiple of setting current |
Acting time | Initial state | Ambient air temperature | |
1 | 1.0In | ≤2h non-tripping | Cold state | +40℃±2℃ | |
2 | 1.2In | ≤2h tripping | Start after 1 | +40℃±2℃ |
Type | Standard power ratings of 3-phase molors 50/60Hz in category AC-3 |
Current setting range |
|||||
220V | 380V | 415V | 440V | 500V | 660V | ||
kW | kW | kW | kW | kW | kW | ||
YCP5-25-ME01 | - | - | - | - | - | - | 0.1-0.16 |
YCP5-25-ME02 | - | - | - | - | - | - | 0.16-0.25 |
YCP5-25-ME03 | - | - | - | - | - | - | 0.25-0.4 |
YCP5-25-ME04 | - | - | - | - | - | 0.37 | 0.4-0.63 |
YCP5-25-ME05 | - | - | - | 0.37 | 0.37 | 0.55 | 0.63-1 |
YCP5-25-ME06 | - | 0.37 | - | 0.55 | 0.75 | 1.1 | 1-1.6 |
YCP5-25-ME07 | 0.37 | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 | 1.6-2.5 |
YCP5-25-ME08 | 0.75 | 1.5 | 1.5 | 1.5 | 2.2 | 3 | 2.5-4 |
YCP5-25-ME10 | 1.1 | 2.2 | 2.2 | 3 | 3.7 | 4 | 4-6.3 |
YCP5-25-ME14 | 2.2 | 4 | 4 | 4 | 5.5 | 7.5 | 6-10 |
YCP5-25-ME16 | 3 | 5.5 | 5.5 | 7.5 | 7.5 | 9 | 9-14 |
YCP5-25-ME20 | 4 | 7.5 | 9 | 9 | 9 | 11 | 13-18 |
YCP5-25-ME21 | 5.5 | 11 | 11 | 11 | 11 | 15 | 17-23 |
YCP5-25-ME22 | 5.5 | 11 | 11 | 11 | 15 | 18.5 | 20-25 |
YCP5-25-ME32 | 7.5 | 15 | 15 | 15 | 18.5 | 26 | 24-32 |
YCP5-80-ME10 | 1.1 | 2.2 | 2.2 | 3 | 3.7 | 4 | 6-10 |
YCP5-80-ME16 | 2.2 | 4 | 4 | 4 | 5.5 | 7.5 | 10-16 |
YCP5-80-ME20 | 4 | 7.5 | 7.5 | 7.5 | 10 | 11 | 14-20 |
YCP5-80-ME25 | 5.5 | 11 | 11 | 11 | 15 | 18.5 | 16-25 |
YCP5-80-ME40 | 11 | 18.5 | 22 | 22 | 25 | 33 | 25-40 |
YCP5-80-ME63 | 15 | 30 | 33 | 33 | 40 | 55 | 40-63 |
YCP5-80-ME80 | 22 | 40 | 45 | 45 | 55 | 63 | 56-80 |