YCQ9HB ATS appliances are suitable for AC 50Hz, rated working voltage 400V and below,rated current 10A to 63A dual power supply system, the power supply system of the two power sources: common power supply (N) and standby power supply (R) at the same time detection, when the power supply occurs undervoltage, phase failure power supply failure that is, automatic switching from the abnormal power supply to the normal power supply (can also be manually switched), to enhance the continuity and reliability of the power supply system in the use of the premises. This improves the continuity, safety and reliability of the power supply system at the place of use.
Switching appliances are widely used in power systems, hospitals, postal and telecommuni cation, fire fighting, hotels, banks, airports, wharves, residential neighborhoods, TV stations, military facilities, shopping malls and other important places where the continuity of power supply is required.
Standards: IEC 60947-6-1.
1. The ambient air temperature is -5 °C ~ +40 °C, and the average temperature within 24h does not exceed 35 °C.
2. The altitude of the installation site does not exceed 2000m above sea level.
3. The relative humidity of the air at the installation site should not exceed 50% at an ambient temperature of +40°C. Higher relative humidity is possible at lower temperatures. For example, in the wettest month with an average minimum temperature of +20°C, the monthly average maximum relative humidity for that month can be up to 90%. Appropriate measures should be taken to prevent condensation due to temperature changes
4. The pollution level is 3. There is no danger of explosion in the surrounding air, and there are no gases or conductive dust that could corrode metals and destroy insulation.
5. The installation category is III.
6. The two power lines are connected to the upper end of the switching appliance and the load line is connected to the lower end, and must not be reversed.
7. The installation site should be free from significant vibration and shock.
Company Code |
Product cod |
Design number |
Frame current |
Number of poles |
Control mode |
Circuit Breaker Disconnect Type |
Rated Current |
Function codes |
YC | Q | 9HB | 63 | □ | □ | □ | □ | □ |
CNC | ATS | CB class | 63A | 2-2 poles; 3-3 poles; 4-4 poles |
R-Auto transfer and auto retransfer, S-Auto transfer and non-auto retransfer, I- Mutual backup |
C-C type; D-D type |
10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
F-grid to generation; T-communication |
Technical data | YCQ9HB-63 |
Rated working current le | 10A,16A,20A,25A,32A,40A,63A |
Rated working voltage Ue | AC 230V/50Hz(2P),AC 400V/50Hz(3P,4P) |
Rated insulation voltage Ui | 500V |
Rated impulse withstand voltage Uimp | 4kV |
Rated short-circuit making capacity | 9.18kA |
Rated making and breaking capacity | 6kA |
Mechanical life | 10,000 times |
Electrical life | 3000 times |
Usage category | AC-33iB |
Electrical grade | CB grade |
Pole | 2P,3P,4P |
Delay time | 0~30s adjustable |
Electromagnetic compatibility environmen | Environment B |
Pollution degree | 3 |
protection class | IP30 |
Installation | Vertical Fixed Installation |
operating method | Automatic/Manual |
switch position | Common position(I),Standby position(Ⅱ),Disconnect position (0) |
Rated control power | AC 230V/50Hz |
Power supply voltage | Undervoltage switching:165V±10% |
Control | Loss of voltage/phase out,undervoltage,overvoltage switching |
Control function | |
Auto/Manual Conversion Mode | ■ |
dichotomous | ■ |
Grid -Power Grid | ■ |
Grid --generators | □ |
self-referral | ■ |
abandon oneselfand not return | △ |
serve as a backup | △ |
Monitor common power supplies and failover | ■Phase failure/loss of voltage,undervoltage,overvoltage faults |
Monitor backup power and failover | ■Phase failure/loss of voltage,undervoltage,overvoltage faults |
Fire control input(passive) | ■ |
Fire Feedback Output | ■ |
Adjustable delay time | ■ |
conversion delay | Os-30s adjustable |
Return delay | Os-30s adjustable |
Common and standby closing indication | ■ |
Common and standby power indication | ■ |
malfunction alarm | ■ |
overvoltage conversion | ■ |
Undervoltage conversion | ■ |
Loss of Pressure Conversion | ■ |
Out-of-phase conversion | ■ |
communication function | □ |
Display Module | light-emitting diode |
Note: " ■ " means this function is available; " □ " means this function is optional; " △ "means Customers require factory adjustments.
1-Mounting hole; 5-Operating handle; 9-Handle padlock;
2-Product model; 6-Wiring terminal; 10-Fuse tube;
3-Company logo; 7-Changeover position indication; 11-Secondary terminal block
4-Controller; 8-Grounding screw;
1- Common power indicator; 5-Normal to backup conversion delay setting;
2- Common closing indicator; 6-Backup to normal return delay setting;
3- Standby power indicator; 7-Auto/Manual switching gear.
4- Standby closing indicator;
Product status | 1 | 2 | 3 | 4 |
Common power supply normal | Ever Bright | |||
Common power closing | Ever Bright | |||
Backup power supply normal | Ever Bright | |||
Standby power closed | Ever Bright | |||
Commonly used circuit breaker release | Adorable | Adorable | ||
Spare circuit breaker release | Adorable | Adorable | ||
Standby conversion delay | Adorable | |||
Standby constant return delay | Adorable | |||
Product Conversion Failure | Adorable | Adorable | ||
Fire switch | Adorable | Adorable |
Line maintenance and fault repair, first switch the switching appliances automatic / manual switching gear to manual, and then switch the switching appliances to the double points position ; pull the handle padlock and lock, can prevent accidents, the diameter of the lock hole is Ø5.5.