Technical data
project name |
performance index |
|
scope of application |
3 phase rat cage asynchronous motor |
|
power bracket |
5.5-450kW |
|
input voltage |
380V ± 15% |
|
supply frequency |
50/60HZ ± 5% |
|
overload capacity |
400%60sec,120% continuous |
|
Adjustable current multiple |
From 1 to 5 times each time |
|
Soft up time |
1-90 Seconds |
|
Module working mode |
over a long period of time |
|
cooling-down method |
forced air cooling |
|
Secondary interace terminal |
on-off input |
3 Road |
relay output |
1 (programmable) or 3 (programmable) |
|
4-20MA |
Route (extension is optional) |
|
RS485 |
1-way (extended as optional) |
|
Protect |
Short circuit speed break, overcurrent, overheat protection, reverse time overload, voltage phase deficiency, imbalance, lnsient stop, undervoltage, overvoltage, underload, starting failure, phase sequence error. |
|
Host overload protection |
Overload and reverse time limit, level 1 -5 is optional |
|
Host current imbalance protection |
Unbalanced trip standard: 5- 100% any two-phase unbalanced trip delay: 1-60 seconds can be set |
|
Host short circuit protection |
Quick break time . 0.18, can be set |
|
Bus function |
Interface : RS485 protocol · ModbusRTU |
|
human-computer interface |
4 Line COG Screen |
|
Language |
Chinese, English |
Technical data
Order number |
Name |
Set the scope |
Windows default |
Explain |
Soft-up parameters
A1 |
Start way |
0~3 |
3 |
0: aging 1: voltage ramp 2: constant current3:current ramp |
A2 |
Starting voltage |
0~100% |
45% |
0,1,2 The starting mode is effective |
A3 |
Initial current |
0~2.5 Times |
2.0 Times |
Method 3 valid |
A4 |
Flow limit multiple |
1.8~6.0 Times |
3.5 Times |
Method 1,2,3 valid |
A5 |
Sudden jump peak |
0~100 |
90% |
|
A6 |
The jump cycle |
0~2.0S |
0.4S |
|
A7 |
Start delay |
0~240.0S |
0.0S |
Delayed start time |
A8 |
Soft up time |
0~90.0S |
20.0S |
All starting modes are valid |
A9 |
Soft stop time |
0~60S |
0S |
Set to 0 no soft stop function, non-0 valid |
A10 |
Joint control delay |
0~240.0S |
0.0S |
Start the delay relay output, use with programmable relay |
A11 |
mode of operation |
0~6 |
3 |
0: Full open 1: keyboard 2: external control 3: keyboard + external control 4: Communication 5:Communication + keyboard 6:communication + external control |
A12 |
Rated current |
0~Current limit |
100A |
Set according to the rated current on the motor nameplate |
A13 |
Upper limitcurrent |
0~200% |
120% |
The relay is set to feed effectively |
A14 |
Lower limit current |
0~120% |
90% |
The relay is set to feed effectively |
A15 |
actuation time |
0~10.0S |
1.0S |
The relay is set to feed effectively |
A16 |
Soft startplus time |
0~60.0S |
0 |
"Soft start time" does not complete the start, automatic extra time |
A17 |
Soft strength |
2.0 Times |
0 |
"Soft start time" does not complete the start, automatic extra time |
Protection parameters
A18 |
Short circuit multiple |
0~12.0 Times |
5.5 Times |
Set greater than (current limit multiple + soft starting force + 0.5), the whole process is effective |
A19 |
Speed break time |
0~2.00S |
0.20S |
Short circuit block (break) time |
A20 |
Overflow multiple |
0~8.0 |
1.2 |
Bypass effective |
A21 |
Overflow time |
0~60.0S |
10.0S |
If the overflow exceeds this value, block the silicon |
A22 |
Overheat time |
0~60.0S |
10.0S |
When oyerheating exceeds this value, blocking the SCR,the whole process is effective |
A23 |
Overload curve |
1~6 |
1 |
Motor reverse time limit protection, reverse time limit curve number, the larger the value, the longer the time, bypass (full pressure) after the effective |
A24 |
Lack of phase time |
0~60.0S |
10.0S |
If the voltage phase deficiency exceeds this value,the SCR is blocked, and the whole process is effective |
A25 |
Current imbalance |
0~100% |
30% |
Current imbalance ratio, soft rise, bypass, soft stop effective |
A26 |
Imbalance time |
0~60.0S |
5.0S |
If the accumulated time of imbalance exceeds this value, block the silicon controller |
A27 |
Underpress ure lower limit |
0~100% |
70% |
Full effective |
A28 |
Overpressure time |
0~60.0S |
2.0S |
If the accumulated time of underpressure exceeds this value, the thyristor is blocked |
A29 |
Overpressure upper limit |
0~150% |
120% |
Full effective |
A30 |
Overpressure time |
0~60.0S |
2.0S |
If the cumulative time of overpressure exceeds this value,the thyristors is blocked |
A31 |
Under-load current |
0~100% |
50% |
Lower undercurrent, bypass and full pressure effective |
A32 |
Adue time |
0~30.0s |
2.0s |
If the cumulative time exceeds this value, the thyristor is blocked |
Order number |
Name |
Set the scope |
Windows default |
Explain |
Protection switch
A33 |
Short-circuiting switch |
Close, open |
Open |
Output short-circuit protection is enabled or prohibited |
A34 |
Overflow switch |
Close, open |
Open |
Overcurrent protection enables or forbids |
A35 |
Overheat awitch |
Close, open |
Open |
Overheat protection enables or prohibited |
A36 |
overload cut-out |
Close, open |
Open |
Motor overload protection is enabled or prohibited |
A37 |
Lack of phases witch |
Close, open |
Open |
Input voltage phase absence protection enabled or prohibition |
A38 |
Imbalance switch |
Close, open |
Open |
Current imbalance (output phase deficiency) protection enabled or prohibition |
A39 |
Instantaneo us stop switch |
Close, open |
Open |
External instantaneous stop fault protection enabled or prohibited, enabling can be set to self-recovery |
A40 |
Undervoltag e switch |
Close, open |
Open |
Input voltage protection enabled or prohibited |
A41 |
Overvoltage switch |
Close, open |
Open |
Input voltage overvoltage protection enable or prohibited |
A42 |
Starting failure |
Close, open |
Open |
Motor is not enabled or prohibited by full speed protection during bypass (or full pressure) |
A43 |
Underload switch |
Close, open |
Open |
Underload protection is enabled or prohibited |
A44 |
Phase sequence switch |
Close, open |
Open |
Phase order error protection enables or prohibition |
Communication parameters : not considered when not used
A45 |
principal and subordinate |
0,1,2 |
0 |
0:Close 1:Host 2:slave |
A46 |
Stop number |
0~32 |
1 |
|
A47 |
Digit capacity |
0~12 |
8 |
Usually set to 8 |
A48 |
Stop bit |
0~2 |
0 |
Usually set to 1 |
A49 |
Even-odd check |
0~2 |
1 |
Usually set to 0 |
A50 |
Baud rate |
0~96 |
8 |
Actual baud rate-baud rate*1200 |
A51 |
Current range |
0~6000 |
1000 |
4 mA corresponds to 0 and 20 macorresponds to range values |
Control
A52 |
Customer privilege |
|
|
Password 10, go to the customer privilege menu |
A53 |
Manufacturer setting |
|
|
Password 111,enter the manufacturer setting menu |