The YCQVA-2 series products are applicable to rated currents of 100A and below, supporting intelligent switching between dual power supplies of mains-to-mains and mains-to-generator. The two input circuits adopt a physical isolation design, fully complying with electrical safety specifications and standards.
It features dual modes of automatic circuit switching and manual free switching for flexible and convenient use. The overvoltage and undervoltage protection thresholds can be customized; automatic power-off protection is triggered immediately when the voltage exceeds the set range. A built-in delayed restart mechanism enables automatic closing and power supply restoration after the grid voltage stabilizes. Meanwhile, it allows independent setting of the current limiting value, with automatic power-off upon overcurrent and self-recovery after fault elimination. The complete machine integrates multiple safety protections including neutral loss, overvoltage, undervoltage and overload, comprehensively preventing hidden risks such as grid voltage fluctuations and current abnormalities. It effectively ensures the long-term stable operation of rear-end electrical equipment and avoids fault damage.| Model | Rated current | Rated supply voltage |
| YCQVA-2 | 63A | AC220V |
| Automatic transfer switch |
63A 80A 100A |
AC220V AC110V |
| Rated supply voltage | AC 2*110V/220V |
| Operating voltage range | AC 80-300V |
| Rated frequency | 50/60Hz |
| Hysteresis | Overvoltage:5V Undervoltage:5V |
| Measurement accuracy | 0.5 class |
| Rated insulation voltage | 450V |
| Output contact | 1NO |
| Electrical life | 105 |
| Switch delay to reserve phases | >0.2s |
| Overvoltage trip delay | 0.1s; ≥350V; 0.02s |
| Undervoltage trip delay | 0.1s; ≥350V; 0.02s |
| Mechanical life | 106 |
| Protection class | IP20 |
| Pollution degree | 3 |
| Altitude | |
| Operating temperature | -5°C~40°C |
| Humidity | ≤50% or 40°C |
| Storage temperature | -10°C~55°C |
| Product size | 63A:90*96*67mm ; 80A/100A:90*103*67mm |
| Voltage accuracy | <1% |
| Rated operating current | 63A/80A/100A |
| Max. operating current | 63A/100A |
| Set character | Technical parameter | Set range | Default value | Step forward | Function description |
| P-1 | Power-on delay time | 1S-999s | 5s | 1s | After external power cut, the time needed for power- on when power recovery. |
| P-2 | Recovery/Switch Time | 1S-999s | 10s | 1s | Is the time required for the line to return to normal or switch to a working line. |
| P-3 | Timed of | OFF-0.1m-999m | OFF | 0.1m | Can be used to time of the device |
| P-4 | Timed on | ON-0.1m-999m | ON | 0.1m | The P-3 timer of parameters must be changed before the timer on parameters can be adjusted. |
| P-5 | Input phase priority selection |
L1-L2 -ATO | L1 | 1 | Operating mode: When L1 or L2 is selected, it's a priority phase selection; ATO: Non-priority mode, fxed to the current phase. |
| P-6 | Over-voltage protection value |
120V-300V -OFF |
270V 140V | 1V | When the voltage of one phase is over the set value, the protector will cut of this phase and switch to the next phase according to the sequence set in P5. When all voltage is over the set value, the protector will cut of all lines. |
| P-7 | Under-voltage protection value |
OFF-80V-210V | 170V 90V | 1V | When the voltage of one phase is under the set value, the protector will cut of this phase and switch to the next phase according to the sequence set in P5. When all voltage is under the set value, the protector will cut of all lines. |
| P-8 | Voltage calibration | ±9.9% | 0 | 0.10% | Correct the voltage error. |
| P-9 | Over-current protection value |
1A-63A/100A - OFF |
63A 80A | 1A | When the current is higher than the set value, the protector will cut of the line. When setting OFF, the protector will turn of over-current protection function. |
| P-10 | Current calibration | ±9.9% | 0 | 0.10% | Calibrate current current value |
| P-11 | Overcurrent protection action time |
0.1S-30s | 1s | 0.1s | When over current, the time needed for protection action. |
| P-12 | Times of continuous over current protection |
OFF-1-20 | OFF | 1 | When the times of continuous over-current protection exceeds the set value, the protector will cut of the line, then it needs to be opened manually. |
| P-13 | Temperature protection |
40°C-120°C | 90°C | 1°C | After temperature protection, the hysteresis value is restored to 10°C. |
| Display | illustrate |
| oc | Overcurrent |
| HT | high temperature |
| TIM | Timed |