YCQVA-2 Automatic Transfer Switch

General

The YCQVA-2 series products are applicable to rated currents of 100A and below, supporting intelligent switching between dual power supplies of mains-to-mains and mains-to-generator. The two input circuits adopt a physical isolation design, fully complying with electrical safety specifications and standards.

It features dual modes of automatic circuit switching and manual free switching for flexible and convenient use. The overvoltage and undervoltage protection thresholds can be customized; automatic power-off protection is triggered immediately when the voltage exceeds the set range. A built-in delayed restart mechanism enables automatic closing and power supply restoration after the grid voltage stabilizes. Meanwhile, it allows independent setting of the current limiting value, with automatic power-off upon overcurrent and self-recovery after fault elimination. The complete machine integrates multiple safety protections including neutral loss, overvoltage, undervoltage and overload, comprehensively preventing hidden risks such as grid voltage fluctuations and current abnormalities. It effectively ensures the long-term stable operation of rear-end electrical equipment and avoids fault damage.  

Type designation

Model Rated current Rated supply voltage
YCQVA-2 63A AC220V
  Automatic
transfer switch
63A
80A
100A
AC220V
AC110V
 

Operating conditions

1. When installing the product, the input terminal must be connected to a circuit breaker. 2. After receiving the product, first connect only one power source to check if the display is normal. 3. The equipment must be installed by qualified professionals. 4. Before operating the device, disconnect all power supplies and do not touch any terminal when the power supply is connected. 5. Verify that terminals are properly connected. 6. Do not use the equipment in places that may be corroded by gas, strong sunlight and rain. 7. Clean equipment with a dry cloth. 8. Failure to comply with these instructions will result in serious injury or serious accident.  

Feature

1. Automatic Transfer Switch: with “priority” phase 2. Microcontroller-based 3. Digital display of working voltage, current 4. Measurement accuracy is 0.5 class 5. Key setting parameter 6. Can set the priority phase sequence 7. DIN rail mounting  

Technical data

Rated supply voltage AC 2*110V/220V
Operating voltage range AC 80-300V
Rated frequency 50/60Hz
Hysteresis Overvoltage:5V Undervoltage:5V
Measurement accuracy 0.5 class
Rated insulation voltage 450V
Output contact 1NO
Electrical life 105
Switch delay to reserve phases >0.2s
Overvoltage trip delay 0.1s; ≥350V; 0.02s
Undervoltage trip delay 0.1s; ≥350V; 0.02s
Mechanical life 106
Protection class IP20
Pollution degree 3
Altitude  
Operating temperature -5°C~40°C
Humidity ≤50% or 40°C
Storage temperature -10°C~55°C
Product size 63A:90*96*67mm ; 80A/100A:90*103*67mm
Voltage accuracy <1%
Rated operating current 63A/80A/100A
Max. operating current 63A/100A

 

 

Display panel

Electrical symbol diagram

 

Wiring diagram

Program description

Set character Technical parameter Set range Default value Step forward Function description
P-1 Power-on delay time 1S-999s 5s 1s After external power cut, the time needed for power-
on when power recovery.
P-2 Recovery/Switch Time 1S-999s 10s 1s Is the time required for the line to return to normal 
or switch to a working line.
P-3 Timed of OFF-0.1m-999m OFF 0.1m Can be used to time of the device
P-4 Timed on ON-0.1m-999m ON 0.1m The P-3 timer of parameters must be changed 
before the timer on parameters can be adjusted.
P-5 Input phase priority 
selection
L1-L2 -ATO L1 1 Operating mode: When L1 or L2 is selected, it's a 
priority phase selection; ATO: Non-priority mode, 
fxed to the current phase.
P-6 Over-voltage 
protection value
120V-300V 
-OFF
270V 140V 1V When the voltage of one phase is over the set 
value, the protector will cut of this phase and switch 
to the next phase according to the sequence set 
in P5. When all voltage is over the set value, the 
protector will cut of all lines.
P-7 Under-voltage 
protection value
OFF-80V-210V 170V 90V 1V When the voltage of one phase is under the set 
value, the protector will cut of this phase and switch 
to the next phase according to the sequence set 
in P5. When all voltage is under the set value, the 
protector will cut of all lines.
P-8 Voltage calibration ±9.9% 0 0.10% Correct the voltage error.
P-9 Over-current 
protection value
1A-63A/100A - 
OFF
63A 80A 1A When the current is higher than the set value, the 
protector will cut of the line. When setting OFF, 
the protector will turn of over-current protection 
function.
P-10 Current calibration ±9.9% 0 0.10% Calibrate current current value
P-11 Overcurrent protection 
action time
0.1S-30s 1s 0.1s When over current, the time needed for protection 
action.
P-12 Times of continuous 
over current protection
OFF-1-20 OFF 1 When the times of continuous over-current 
protection exceeds the set value, the protector will 
cut of the line, then it needs to be opened manually.
P-13 Temperature 
protection
40°C-120°C 90°C 1°C After temperature protection, the hysteresis value is 
restored to 10°C.

 

Setup menu

Fault Description

Display illustrate
oc Overcurrent
HT high temperature
TIM Timed

 

Overall and mounting dimensions (mm)