Type designation
1. Rated current in scope of frame current
2000 Type-in: 630A, 800A, 1000A, 1250A, 1600A, 2000A;
3200 Type-in: 2000A, 2500A, 3200A;
6300 Type-in: 4000A, 5000A, 6300A;
2. Pole number
3-default, 4-4 pole
3. Installation
Fixed type-horizontal, vertical
Draw out type-horizonal, vertical
Note: 2000 type have vertical wiring, others are horizontal wiring
4. Control unit
L type-dial switch mode, over-current protection (overload, short delay,
instantaneous).
2M type-digitaldisplay,over-current protection (overload, shortdelay,
instantaneous), 4P or 3P+N have earthing protection (3M type is LCD display).
2H type-communication function, digital display, over-current protection
(overload, short delay, instantaneous), 4P or 3P+N have earthing protection (3H
type is LCD display).
5. Common use accessory
Closing electromagnet-AC230V, AC400V, DC220V
Undervoltage release-AC230V, AC400V, undervoltage instantaneous,
undervoltage time-delay
Release (close) magnetic iron-AC230V, AC400V, DC220V
Electric operation mechanism-AC230V, AC400V, DC110V, DC220V
Auxiliary contact-standard type (4a4b), special type (5a5b, 6a6b)
Note: a-normal open, b-normal close
6. Optional accessory
Mechanical inter-lock:
one circuit breaker (1lock+1key)
two circuit breaker (steel cable inter-lock, connecting rod inter-lock, 2lock+1key)
three circuit breakers (3locks+2keys, connecting rod inter lock)
Automatic power transfer system
Current transformer connected with neutral lead
Operation Conditions
Operating conditions |
Item |
Description |
Ambient temperature |
-5℃~+40℃ (except special order products) |
Altitude |
≤2000m |
Pollution grade |
3 |
Safety category |
Main circuit and undervoltage tripping coil is IV, other auxiliary and control circuit is III |
Installation position |
Vertical installed, tilt not exceed 5 degree |
Environmental protection |
Most of parts use recyclable and degradable materials |
Isolating function |
With isolating function |
Specifications
Curves
Data
Type |
|
YCW1-2000 |
YCW1-3200 |
YCW1-6300 |
Pole |
|
3P, 4P |
3P, 4P |
3P, 4P |
Using category |
|
B |
B |
B |
Rated current In |
A |
630, 800, 1000,1250, 1600, 2000 |
2000, 2500, 3200 |
4000, 5000, 6300 |
Rated frequency |
Hz |
50 |
50 |
50 |
Rated operation voltage Ue |
V |
400, 690 |
400, 690 |
400, 690 |
Rated insulation voltage Ui |
V |
800 |
800 |
800 |
Arcing distance |
mm |
0 |
0 |
0 |
Rated impulse withstanding voltage Uimp |
V |
8000 |
8000 |
8000 |
Rated operation short circuit breaking capacity Ics (O-t-CO) |
400V |
kA |
50 |
80 |
100 |
660V |
kA |
40 |
50 |
75 |
Rated limiting short circuit |
400V |
kA |
80 |
80 |
120 |
breaking capacity Icu (O-t-CO) |
660V |
kA |
50 |
65 |
85 |
Rated short time withstanding current Icw (O-t-CO, AC400V 0.4S) |
400V |
kA |
50 |
65 |
85 |
Operation life |
Per hour |
times |
20 |
20 |
10 |
Electrical |
times |
1000 |
500 |
500 |
Mechanical |
times |
10000 |
5000 |
5000 |
Full breaking time |
|
ms |
20~30 |
20~30 |
20~30 |
Full closing time |
|
ms |
55~70 |
55~70 |
55~70 |
Power consumption |
3P |
W |
360 |
1200 |
2000 |
4P |
W |
450 |
1750 |
2300 |
Resistance of each pole |
Fixed type |
μΩ |
11 |
9 |
- |
Draw out type |
μΩ |
20 |
14 |
10 |
Dimensions (L ×W × H) |
3P fixed type |
mm |
362 ×323 ×402 |
422 ×323 ×402 |
|
3P draw out type |
mm |
375 ×461 ×452 |
435 ×471 ×452 |
|
4P fixed type |
mm |
457 ×323 ×402 |
537 ×323 ×402 |
|
4P draw out type |
mm |
470 ×461 ×452 |
550 ×471 ×452 |
|
Approximate weight |
3P fixed type |
kg |
41 |
55 |
|
3P draw out type |
kg |
71 |
95 |
245 |
4P fixed type |
kg |
51.5 |
65 |
- |
4P draw out type |
kg |
86 |
115 |
260 |
Overload protection data
Overload protection |
YCW1-2000~6300 |
Adjust scope Ir1 |
|
(0.4-1)In (pole difference 2%) |
1.05 Ir1 |
h |
2h non-tripping |
1.3 Ir1 |
h |
≤1h tripping |
1.5 Ir1 |
s |
15 |
30 |
60 |
120 |
240 |
480 |
2.0 Ir1 |
s |
8.4 |
16.9 |
33.7 |
67.5 |
135 |
270 |
Accuracy |
% |
±15 |
Short circuit, short time delay |
|
Adjust scope Ir1 Ir2 |
|
(0.4-15)In (pole difference 2%) |
Delay time tr2 |
ms |
100, 200, 300, 400 |
Accuracy |
% |
±15 |
Short circuit, instantaneous |
|
|
YCW1-2000 |
YCW1-3200 |
YCW1-6300 |
Adjust scope Ir1 Ir3 |
|
1In-50kA |
1In-75kA |
1In-100kA |
Accuracy |
% |
±15 |
±15 |
±15 |
Load monitoring output |
YCW1-2000~6300 |
Load adjust scope Ic1 |
|
(0.2-1)In (pole difference 2%) |
Delay time tc1 |
|
tr1 ×0.5 |
Load adjust scope Ic2 |
|
(0.2-1)In (pole difference 2%) |
Delay time tc2 |
|
tr1 ×0.25 (anti-time limit) |
Accuracy |
s |
60 (set time limit) |
% |
±10 |
Overall and mounting dimensions
Installation and figure dimension of YCW1-2000A fixed type circuit breaker
Installation and figure dimension of YCW1-3200A fixed type circuit breaker
Installation and figure dimension of YCW1-4000A fixed type circuit breaker
Installation and figure dimension of YCW1-6300A fixed type circuit breaker
Installation and figure dimension of YCW1-2000A draw-out type circuit breaker
Installation and figure dimension of YCW1-3200A draw-out type circuit breaker
Installation and figure dimension of YCW1-4000A draw-out type circuit breaker
Installation and figure dimension of YCW1-4000A(4P) draw-out type circuit breaker
Installation and figure dimension of YCW1-6300A draw-out type circuit breaker
Installation and figure dimension of draw-out type circuit breaker (Inm=3200A 3P 4P)
Dimension of panel hole see picture and table Unit:mm
Interlock device of circuit breaker see picture Unit:mm
Interlock device of vertical install circuit breaker
Interlock device of horizontal install circuit breaker
Characteristic of intelligent controller
|
Basic function |
|
Overload longtime-delay/anti-time limit protection |
Short circuit short time-delay/anti-time limit protection |
Short circuit short time-delay timing protection |
Short circuit instantaneous protection |
Insulate earth fault protection |
Display function |
|
|
Current (select 1) |
Digital display |
Can display L1, L2, L3, ImaxI G(earth), IG(Neutral) |
Voltage (select 2) |
Digital display |
Can display U12, U23, U31, Umin |
Power (select 2) |
P |
Power factor (select 2) |
|
COSΦ |
Warning function |
|
|
Over current fault warning |
Light-emitting diodes on panel |
After fault trip indicator light corresponding |
Fault category identification |
Light-emitting diodes on panel |
Overload log time-delay |
|
Short circuit short time-delay |
Short circuit instantaneous |
Earth fault |
Fault phase sequence |
Digital display |
Display the fault phase sequence |
Current |
|
Breaking current |
Time display |
|
Breaking time |
Contact loss indication |
Digital display |
Display percentage of loss |
Self-diagnosis function |
|
Send the error signal |
Testing function |
|
|
Panel key |
Tripping |
Test the time current characteristic of release and situation of operation device |
Remote monitoring function |
Non-tripping |
Test the time current characteristic of release |
Remote monitoring code signal optocoupler |
Relay (contain power) module |
Output of various working condittion |
Communication function |
|
|
Communicate type |
RS485(communication) I/O |
User should consult with the manufacturer |
Electrical accessories
Under-voltage release |
Rated working voltage Ue(V) |
AC400 AC230 |
|
Acting voltage (V) |
(0.35~0.7) Ue |
Reliable close voltage (V) |
(0.85~1.1) Ue |
Non close voltage (V) |
≤0.335Ue |
Power loss |
12VA (YCW1-1000 5VA) |
Shunt release |
Rated control power voltage Us(V) |
AC400 AC230 DC220 DC110 |
|
Acting voltage (V) |
(0.7~1.1) Ue |
Power loss |
40VA 40W (YCW1-1000 5VA) |
Open time |
less than 30ms |
Close electromagnetic iron |
Rated control power voltage Us(V) |
AC400 AC230 DC220 DC110 |
|
Acting voltage (V) |
(0.85~1.1) Ue |
Power loss |
40VA 40W (YCW1-1000 5VA) |
Open time |
less than 70ms |
Motor operating device |
Rated control power voltage Us(V) |
AC400 AC230 DC220 DC110 |
|
Acting voltage (V) |
(0.85~1.1) Ue |
Power loss |
40VA 40W (YCW1-1000 5VA) |
Open time |
less than 5s |