Home Categories Send inquiry

YCB3RL-63 RCBO Electromagnetic

General

YCB3RL-63 series electromagnetic residual current operated circuit breaker is mainly suitable for AC distribution networks with a rated working voltage of 230V or 400V at 50/60Hz and a rated current of 63A. Used for indirect contact protection of people, and can also be used to prevent fire hazards caused by insulation damage to circuits and equipment,resulting in ground fault currents.

Feature

1. Protection against the effects of sinusoidal alternating earth fault currents.

2. The leakage protection feature does not require an auxiliary power supply.

3. Not affected by voltage fluctuations in the power grid.

Type designation

 

Model Shell grade
current
Poles Rated
current
Rated residua
   operating
Type
YCB3RL 63  1P+N 63  100mA A Type
RCCB  Elec-
tromagnetic
63  1P+N
3P+N
  Default:
  30mA
  100mA
  300mA
Default:
AC  Type
A   Type
10 
16 
20 
25 
32 
40 
50 
63 
Note:This product cannot be assembled with attachments

 

Technical data

 

Type Standard    
Electrical
features
Leakage type   Electromagnetic type
Rated current In A 6,10,25,32,40,50,63
Type(wave form of the earth leakage sensed)   A,AC
Poles P 1P+N,3P+N
Rated voltage Ue V 230/400
Insulation voltage Ui V 500 
Rated frequency Hz 50/60
Rated breaking capacity Inc=I△c A 6000 
Rated impulse withstand voltage(1.2/50)Uimp V 6000 
Dielectric test voltage at ind.Freg.for 1min Kv 2.5 
Rated sensitivity I△n A 0.01,0.03,0.1,0.3,
Rated residual making and breaking capacity I△m A 500(In≤40A);630(In=50A/63A)
Pollution degree  
Mechanical
features
Electrical life times 4000 
Mechanical life times 8000 
Protection degree   IP20
Storage temperature -25~+70
Ambient temperature(with daily average≤35℃) -5~+40
  Terminal connection type   Cable/Pin-type busbar
Terminal size top/bottom for cable   mm² 25/35
  AWG 18-3/18-2
Terminal size top/bottom for busbar   mm² 10/16
  AWG 18-8/18-5
Tightening torque   N*m 2.5 
In-lbs 22 
Mounting   On DIN rail EN60715(35mm)by means of fast clip device
Connection   From top or bottom

Overall and mounting dimensions(mm)